RVersion 2.2Produced in Oct. 1997SHARP Programmable ControllerNew Satellite W seriesModel NameNetwork moduleJW-20CMRemote I/O slave moduleJW-20RSUser’

Seite 2

22·1Chapter 2 Safety Precautions2-1 Installation● Do not install or store the JW-20CM in the following conditions.• Direct sunlight• Ambient temperat

Seite 3 - Safety Precautions

9·29Station number 00(8) Station number 01(8) Station number 02(8) Station number 03(8): Sending area: Receiving areanoitcnuF stnetnoCknilyaleRnoitaci

Seite 4 - Prohibit

9·39(2) Register link functionMainly used for sending and receiving numerical data.[Example] In the case of sending 1 byte data from a master station

Seite 5

9·49[2] Data link (Memory capacity save function)The memory capacity save function is to provide a part of the data link area in the slave stationdata

Seite 6 - - User’s Manual

9·59[3] Link function with specific station (F200/F201 link function)There is a function for communicating data other than the parameter setting value

Seite 7 - Table of contents

9·69[4] SEND/RECEIVE functionDifferent from the data link, the SEND/RECEIVE functions are functions which exchange the data ofthe required station of

Seite 8

9·79(1) Instruction systemThe PC's application instruction F-202/203 (open channel), F-204 (sending instruction), and F-204(receive instruction)

Seite 9 - Chapter 1 Outline

9·89[Example ] In case of writing data of 8 bytes to slave station 03(8)Module number installing own station JW-20CM : 2Channel number using own stati

Seite 10 - Chapter 2 Safety Precautions

9·99(2) Data memory starting systemThe data memory starting system is the system which starts the SEND/RECEIVE functions withoutusing exclusive instru

Seite 11 - Joint using a

9·109*Input/OutputInputOutputOutputOutputOutputOutputOutputOutputOutputOutputOutputOutputAreaFLAGSTIMERG (7th bit)TYPE(0 bit to 6th bit)ST1R_SLST2nADR

Seite 12 - 2-5 Maintenance

9·119[Example] In case of writing 8 bytes data to slave station 03Module number installing own station JW-20CM : 2Channel number using own station JW-

Seite 13

22·2Coaxial cableJW-20CMTurn “ON” shield ground Rack etc.Electric welderNote: In case enough conductivity is not established.JW-20CMTurn “ON” shield g

Seite 14 - 4-1 JW-20CM

9·1299-3 Data transfer required time and communication delaytime(1) Required time for data transferThis is the time required for the master station to

Seite 15 - Set at delivery

9·139(2) Communication delay timeThe communication data on the satellite net may have the delay shown below. ① Delay of input module② Time require

Seite 16 - 4-2 JW-20RS

9·149(3) Data transmission between master PC and slave PCProviding synchronous transfer gives positive data communication.[An example of synchronized

Seite 17

9·1599-4 Expansion of networkThe JW-20CM can transmit data between 64 stations at maximum. If more than 64 stations arerequired for data link, you can

Seite 18 - Chapter 5 Installation

9·169MasterSlave01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 20 21 Slave20 21 22 23 24 25 73 74 75 76 77    : Master stationSlave

Seite 19

9·1799-5 Switch setting of master station or slave stationOperation procedureIn brackets: See page in Chapter 9StartPower “OFF” master/slave stationRe

Seite 20 - Port number

9·189Turn master module and slave modulepower “OFF.”Remove the setting switch cover ofnetwork module JW-20CM.·With your fingertips over the top and bo

Seite 21 - 2 rack panel max

9·199From the previous pageSet LT (termination resistance) switch• When master module or slave module is ateither end the communication line, make sur

Seite 22

9·209From the previous pageSet LG (shield ground) switch· For communication lines, use a coaxial cable.· As coaxial cable is an unbalanced circuit,gro

Seite 23 - Module attachment

9·219From the previous pageAttach label· Attach the data link label to this module, makesetting “data link function” clear.· Write “STATION NO.” on th

Seite 24 - The system consists of the

22·32-3 Treatment● For ventilation, holes are provided in the cabinet to prevent a temperature rise. Do not block theventilation holes. Good ventilat

Seite 25 - 1 mm in order not to

9·2299-6 Setting contents of slave station parameters When the JW-20CM is used as a slave station, set the following items for parameters.※ 1 Set

Seite 26 - When the adjustment

9·239Set top address in communication storage areawhen using data memory starting system of SEND/RECEIVE functions

Seite 27 - KEDAADFS

9·249ReferenceConnect support tools· Connect a support tool with the JW-20CMand prepare the setting parameter.<Usable support tools>JW-13PG/12PG

Seite 28

9·259Screen display of JW-13PGアドレス ADRS モニタ MNTR 書 込 ENT 7 5F 0ASTEP (+) 2 0AC 0A C ADisplay the contents of address 007500(8)Write setting val

Seite 29

9·269From the previous pageSet PC model of each station [HEX (hexadecimal), byte]· Assign model type of the communication target station from ZW and

Seite 30 - Chapter 7 Wiring

9·279From the previous pageSelect system in each channel in SEND/RECEIVE function“When PC is JW model and the SEND/RECEIVE function is used”To the nex

Seite 31

9·289LowerUpper· Set the number of sending bytes in decimal on the parameter address 007720 to 007721(8).From the previous page Set the number of

Seite 32

9·299File address: OCT (octal), wordFile number/flag: HEX (hexadecimal), byteFrom the previous pageSet top address of relay link area.· Set file addre

Seite 33

9·309RemarksFrom the previous pageSet whether the station number information should be output or not· Set whether the station number information shoul

Seite 34 - 7-6 Check after wiring

9·319From the previous pageEnter communication error detection interval [DCM (decimal), byte]· If the JW-20CM does not receive data from a station wit

Seite 35

3·13Chapter 3 System Configuration(Example of system configuration)Slave station 77(8)JW-22CMSlave station 77(8)JW-20RSSlave station 03(8) J-boardPCDa

Seite 36

9·329Write 81(H)Writing to the EEPROM of the JW-20CM, start operation [HEX (hexadecimal), byte]From the previous page· Write “81(H)” into parameter

Seite 37

9·3399-7 Setting contents of master station parameters[1] Setting contentsWhen the JW-20CM is used as a master station, set the following items for pa

Seite 38

9·349metI sserddA )8(laitinIeulav)H()egnargnittes(stnetnoC※ ⑮ evalsfosutatsnoitcennoCnoitats)tuptuoedocrorre(057700ot75770000noitatshcaeotgnidnopserro

Seite 39 - Chapter 8 Remote I/O

9·359Slave station 01(8)(Data memory)Master station 00(8)  (Data memory)Register link area(Within a total of 2048 bytes)Relay link area(Within a total

Seite 40

9·369(2) In case that setting the data link ( V5 memory capacity save function) when the masterstation and all slave stations are JW-20CM.Memory addr

Seite 41 - × 8 points)

9·379• An example of register link area map for the setting of the data link (the save memory function)to slave station 01 and 03 and data link (the s

Seite 42 - Processing of PC side

9·389Select system of each channel in SEND/RECEIVE function[3] Setting procedureIn brackets: See page in chapter 9Start slave station PC operationTurn

Seite 43

9·399• Turn to program mode (stop PC operation). Setting of parameters is only available when the PCis in program mode.(Operation example of JW-13PG)•

Seite 44

9·409From the previous pageSet top address of the relay link area on the master station [OCT (octal), word]• Set file address(8) to parameter addres

Seite 45 - Hold time [ms]

9·419コ 0210コ 0220コ 0224コ 0233コ 0400コ 0420コ 0430コ 0437コ 0740コ 0767コ コ コ コ コ コ コ コ コ コ コ 020002100214074007670223コ 0770077004000420043004371902719030190

Seite 46

4·14Chapter 4 Name and Function of Each Part4-1 JW-20CM(View removing the cover on the setting section)① Indication lampsLamps light ON/OFF indicates

Seite 47

9·429• Set “01(H) (=001(8))” in parameter address 004002(8) and change to “relay/register link.”(Operation example of JW-13PG)LowerUpper00(H) ·

Seite 48

9·439From the previous pageWrite 000200(8) in parameter ad-dresses 004004 to 004005(8).Write 000(8) (=00(H)) in parameter address 004006(8).Write 0000

Seite 49 - Less than 1 km

9·449From the previous pageSet top address of register link area on slave station 01 to 77(8) (at standard function)/number of offset bytes (at memory

Seite 50

9·459From the previous pageSet the number of sending bytes of the master station relay link [DCM (decimal), word]• Set in parameter addresses 005000

Seite 51

9·469toFrom the previous pageSet the number of sending bytes of the master station register link [DCM (decimal), word]• Set the number of sending byt

Seite 52

9·479From the previous pageSet time-out time of SEND/RECEIVE function [DCM (decimal), byte]“When PC is JW model and the SEND/RECEIVE function is used

Seite 53 - 2ledomWJfoeludomO/I

9·489From the previous pageSet PC model of each station [HEX (hexadecimal), byte]“When PC is JW model and the SEND/RECEIVE function is used”• Assign

Seite 54

9·499From the previous pageSelect system in each channel in SEND/RECEIVE function“When PC is JW model and the SEND/RECEIVE function is used”To the nex

Seite 55

9·509From the previous page“When PC is JW model and the SEND/RECEIVE function is used”Set top address in communication information storage area when u

Seite 56 - Write in label

9·519Write 80(H) to address007767(8)Set top address of flag areaFrom the previous pageFile address: OCT (octal), wordFile number/flag: HEX (hexadecima

Seite 57 - O: Necessity for setting

4·24③ Support tool connection connectorConnect a support tool and set parameter etc.④ Setting switchSet functions of JW-20CM.· MODE switch ... Select

Seite 58 - In brackets : See page

9·529Writing to the EEPROM of the JW-22CM, start operation [HEX (hexadecimal), byte]From the previous pageWrite 81(H)•Write “81(H)” into parameter a

Seite 59 - Not setting dummy I/O

9·5399-8 Error and treatmentOperation status of the JW-20CM can be check by indication lamps, flags, or system memory.(1) Indication lampIndication la

Seite 60 - Bit pattern

9·54980○○○○○○○○○○○○○○○○●●●●40○○○○○○○○○○○○○○○○○○●●20○○○○○○○○●●●●●●●●●●○●10○○○○●●●●○○○○○○○●●●○●8○○○○○○●●○○○○●●●○●●○●4○○○●○○○●○○○○○○●○●●○●2○●●○○●○●○○●●●●

Seite 61

9·559(2) FlagFlag area is 24 bytes from the “flag top address” set in the master station/slave station parameters.① Flag table [ In case of flag top a

Seite 62

9·569② In the case of a master station (PC 00)· Communication monitor flagThis flag is used to monitor the communication condition with other stations

Seite 63

9·579· Operation condition monitor flag [2]This flag is used to monitor the abnormal stop of each slave station when the communication witheach slave

Seite 64

9·589③ In the case of slave station (PC 01 to 77(8))· Communication monitor flagThis flag is used to monitor the communication condition with other st

Seite 65

9·599· Operation condition monitor flag [2]This flag is used to monitor the abnormal stop of each station when the communication with eachstation is n

Seite 66

9·609④ Monitor operation condition by each station PCBy creating a program having the flags shown below in each station’s PC, the JW-20CM canmonitor t

Seite 67 - (Light OFF)

9·61901 ROM error, upper CPU02 RAM error, upper CPU032 port RAM error against PC, upper CPU04 2 port RAM error againstcommunication CPU, upper CPU11 R

Seite 68

4·344-2 JW-20RS① Indication lampsLamps light ON/OFF indicates operation condition.② 30Hn mark (Applied to JW30H)JW-20RSs having 30Hn mark can commun

Seite 69 - (8) = 81(H))

9·629• When any of errors “01(H)” to “18(H)” occurs among the error codes listed on the previous page, the JW-20CM stores error code “53(H)” (optional

Seite 70

9·639(4) Recovery method at communication errors① Check flow chartFirst communication?Does the error occur continuously?RecoverySee “When the communic

Seite 71

9·649② Check cable/connectorAs errors on the junction from the main cable to the drop cable or the contact failure on theconnecting point of each stat

Seite 72 - >00000 OCT 014

9·65903(8)Remove the connector on point A, and turn ON the termination resistance of the master station.07(8)06(8)05(8)Masterstation04(8)BD7OFFA CDisc

Seite 73

9·669③ During initial communication (start-up of the system)Lighting error code 6F(H)· When the master station indicates error code 6F(H) and the COMM

Seite 74

9·679· When the master station is normal and the error code 6F(H) of a slave station lights.The cause may be a faulty setting of the slave station par

Seite 75

9·689Other cases• Check the switches of the JW-20CM (see check item)• Check optional cable of PC (The JW-20CM does not operate normally without an opt

Seite 76

9·699④ When the communication error occurs instantaneously.Cause may be:• Noise on the communication line.• Fault of a communication module.• Fault of

Seite 77

9·709StartTurn “OFF” the PC powerRemove the cables from the JW-20CMRemove the JW-20CM from the rack panelSet the switches of the new JW-20CMInstall th

Seite 78 - >00004 0 101000

10·110Chapter 10 Computer link10-1 Description for computer link· You can transmit data between JW-20CM and host computer having a network module ZW-9

Seite 79

4·44③ Support tool connection connectorConnect a support tool and set parameter etc.④ Setting switchSet functions of JW-20RS.· MODE switch ... Select

Seite 80 - >00202 DCM 010

10·21010-2 Communication methodThe host computer communicates with each station number one by one.① The host computer instructs station number/communi

Seite 81 - □■■■■■■■

10·31010-3 Switch settingSame as setting switch of data link. (See page 9·17 to 9·21)When you was already used for data link, setting switch is unnece

Seite 82

10·41010-4 CommandFor communication format etc., see network module ZW-98CM/ZW-20AX etc. instruction manual ofhost computer side.Read out relay (1 poi

Seite 83 - (8) etc

10·510Read out current value of register/file register (1024 bytes max./ one time)Function Read out current value that specified register/file registe

Seite 84 - 8-4 Error and treatment

10·610Write in same data to register/file registerFunction Write in same data that specified register/file registerCommand code 12(H) (FRG)Writing mo

Seite 85

10·710Read out current value of timer/counter/MDFunction Read out current value that specified timer/counter/MDCommand code 03(H) (MTC)Writing mode a

Seite 86 - Indication lamp

10·810Read out current value of system memory (256 bytes max./one time)Function Read out current value that specified system memoryCommand code 04(H)

Seite 87

10·910Read out program memory (512 steps max./one time)Function Read out contents that specified program memory using machinelanguage.Command code 05(

Seite 88

10·1010Change the setting value of timer/counter (1 point unit)Function Change the assigned value of the timer/counter to any value.Command code 16(H)

Seite 89 - Slave station 77(8)

10·1110Read out operation status of PCFunction Read out PC operation status of specified stations.Command code 20(H) (MPC)Writing mode assignment NoO

Seite 90

5·15Chapter 5 Installation5-1 JW-20CM(1) Installation of cable for option moduleInstall the optional cable on the basic rack panel that installed JW-2

Seite 91

10·1210Read out program memory capacityFunction Read out program memory capacity of specified stations.Command code 21(H) (VLM)Writing mode assignmen

Seite 92

10·1310Read out status of write modeFunction Read out status of write mode that specified stations.Command code 22(H) (SWE)Writing mode assignment No

Seite 93

10·1410Read out bit status of parameter memoryFunction Read out parameter memory status of ZW/JW-20CM that specifiedstations.Command code 08(H) (PML)

Seite 94

10·1510Letters in brackets arecommand name of BASICmode.Letters in brackets arecommand name of BASICmode.Set at link operation(Parameter address007777

Seite 95

10·1610Read out date (PC of JW model)Function Read out date that specified stations.Command code 23(H) (MDY)Writing mode assignment NoOperation condi

Seite 96

10·1710Read out times (PC of JW model)Function Read out times that specified stations.Command code 24(H) (MTM)Writing mode assignment NoOperation con

Seite 97

10·1810Correct time (PC of JW model)Function Correct time that specified stations.Command code 35(H) (ACL)Writing mode assignment 1 or 2Operation co

Seite 98

10·1910Read out data by F-200 instructionFunction Read out data that specified station using application instructions F-200.Command code 40(H) (F200)

Seite 99 - Chapter 9 Data Link

11·111Chapter 11 Support ToolsSelect “Read out PARAM” and press the “Enter” key.Start reading to memory of the personal computer.The following support

Seite 100 - 9-2 Communication method

11·211④ Record onto a floppy disketteWrite (record) the memory contents of the personal computer onto a floppy diskette.Select “FD TRANS.”Select “Save

Seite 101

5·25② Attach the connectors in the optional cable one after another, starting from the left side.Basic rack panel JW-4BU6 mounting screwsPay close att

Seite 102

11·311(2) Load① Load to the personal computerLoad the contents of the floppy diskette into the memory of the personal computer.After selecting “Execut

Seite 103

11·411③ Load to the JW-20CMAfter stopping operation, load the memory contents of the personal computer into the JW-20CM.④ Start operation of the JW-20

Seite 104

11·51111-2 Remote function(1) Remote programming and remote monitorThis paragraph describes the operation procedure of any other station's PC whi

Seite 105

11·611① Function<Standard network connection><Expansion network connection>The following operations are possible for “n” station and other

Seite 106 - Target station

11·711② Operation exampleThis paragraph describes an operation example using the multipurpose programmer: JW-50PG.For operations with other support to

Seite 107 - 64 bytes

11·811<Standard network connection>Set “standard” in network configuration.Set “satellite net” or “SUMINET” in target station model.Set the targ

Seite 108

11·911(2) Parameter setting by remote functionThis paragraph describes how to set the parameters of other stations’ network module connected onthe sat

Seite 109

11·1011⑥ Setting parameterAfter finishing communication with the target station, set the parameters remotely.Return to initial menu.Turn the PC of the

Seite 110

12·112Chapter 12 Specifications12-1 JW-20CM(1) General specifications[Outline dimension drawings](Unit : mm)metI snoitacificepSerutarepmetegarotS07+ot

Seite 111

12·212(2) Communication specificationsCommunication methodTransmission rateTransmission formatCoding methodCheck methodSync methodModulation methodCom

Seite 112 - 02000 02030

Thank you for purchasing the network module (JW-20CM), remote I/O slave module (JW-20RS) for theSHARP programmable controller.Read this manual thoroug

Seite 113 - 9-4 Expansion of network

5·35(2) Installation of JW-20CMAttach the basic rack panel using the two attachment screws.Before installation or removal, make sure to shut OFF the p

Seite 114 - : Slave station

12·312(3) Specifications of each function① Specifications of remote I/O slave station② Data link specifications③ Computer link specifications* The amo

Seite 115

12·41212-2 JW-20RS(1) General specifications[Outline dimension drawings](Unit : mm)(2) Communication specificationsCommunication specifications is sam

Seite 116

13·113Chapter 13 Appendix13-1 Maintenance and checkCheck wiring, installation, and switch settings.ONCommunication cableJW-20CM/20RSNot parallel with

Seite 117 - Terminator: ME-75

13·21313-2 Switch setting table(1) JW-20CM (network module)(2) JW-20RS (remote I/O slave module)CBA987654098765432109876543213210FED200OFFONMODESTA.NO

Seite 118 - Turn “ON” shield ground

13·313Setting method (value, example)(Operations when a slave station error occurs)• Remote I/O operation (communication) stops• The PC continues oper

Seite 119

13·413(2/6)Setting method(value, example)Fix•Use the addresses 000006 to 000177(8) listed below when the manual allocation mode is selected. Theseaddr

Seite 120 - 11·7 and 11·8

13·513Setting method (value, example)64 points (8 bytes), no. of slave stations:max. 63 sets.128 points (16 bytes), no. of slave stations:max. 32 sets

Seite 121 - When not using memory

13·613000301Address(8)Set contents(Decimal, bytes)In case of 100 bytes → 100(D)Blanks between slavestations 1 and 2(0 to 255 bytes)○− ○−FixManualJW-PC

Seite 122 - Screen display of JW-13PG

13·713• Set the addresses 000600 to 000777(8) when the master station PC is JW model and uses a special I/Omodule for slave station.• Initial value of

Seite 123

13·813003764to003767(Octal, word)(Hexadecimal,byte)Flag top addressWhen コ0200, set to 000200(8)(Set by file address)When file No. 2, set to 02(H)00376

Seite 124

5·455-2 JW-20RSChoose type of basic rack panel of the remote I/O slave module (JW-20RS) considering kinds andnumber of I/O modules to be installed.Whe

Seite 125 - Setting

13·913• Initial value of the address 004000 to 004377(8) are all 00(H).※ When 00(H) is set, the value becomes the same top address of the master stati

Seite 126 - >07720 D 00004

13·1013※ When 00(H) is set, the value becomes the same top address of the master station regardless of thesetting value of 004404 to 004405(8).• Initi

Seite 127 - >07732 0 000000

13·1113• Initial value of the address 005000 to 005177(8) are all 00(H).Address(8)005000005001005002005003Setting method (value, example)005004 to 005

Seite 128 - HAM4-WJ,AM4-WZ7,6,5,4,3,2,1,0

13·1213(4/7)005300 to 005301005302 to 005303005304 to 005305005306 to 005307005310 to 005311005312 to 005313005314 to 005315005316 to 005317005320 to

Seite 129

13·1313(5/7)• Initial value of the address 007501 to 007577(8) are all 00(H).Address(8)007501007502007503007504007505007506007507007510007511007512007

Seite 130 - Contents

13·1413Set contentsPC model of slave station 01(8)Setting method (value, example)00(H)80(H)81(H)91(H)PC is ZW model or JW model, ZW-20CM iswithout JW

Seite 131

13·1513Instruction systemData memory start systemInstruction systemData memory start systemInstruction systemData memory start systemInstruction syste

Seite 132

13·1613Stop operation of the data linkStart operation of the data linkWriting to EEPROM or operation stop operationWriting to EEPROM or operation star

Seite 133 - bytes bytes bytes

13·1713•Use addresses 000001 to 000017(8) listed below when the I/Os are the JW type.If ZW type I/Os are used, no setting is required.(2) JW-20RS• Ini

Seite 134 - 24 24 24

13·181316 points output32 points output64 points output (JW-62SC)Vacant slot 00↑Lower bits are dummy I/O points16 points output32 points output64 poin

Seite 135

5·55(1) Installation of power supply moduleAttach the end left of rack panel using the two module attachment screws.Rack panel attachment screwPhillip

Seite 136

13·1913• Set page 8·19 for initial values of the addresses above.Slot: 1 Slot: 0D7 6 5 4 3 2 1 0)8(sserddA stnetnocteS )elpmaxe,eulav(

Seite 137 - →Bit pattern

13·201313-4 Address map of data memory(File 0)Relay link area Register link areaFlag areaRegister link areaFlag areaRelay link area sserddayromeM egna

Seite 138 - After converting to octal

13·2113sserddayromeM egnargnitteSsserddatiB)8(=sserdda1stniop1sserddaetyB)8(=sserdda1stniop8sserddaeliF)8(8=sserdda1stniopH07WH001W001/07/05WJH001/H07

Seite 139 - (4 bytes)

13·221313-5 Instructions used with the F200 and F201 link function(1) F-200F-200→ PORTF-200→PORTASKn@ SPORTnSymbolTransfer task number "n" a

Seite 140 - 004004(8)

13·2313Setting range for "S"· Rising edge of the input signal (OFF to ON) [ ※ 3]· S+3 to S+11 are transferred regardless of the input signal

Seite 141 - 004010 to 004011(8)

13·2413(2) F-201F-201PORT →SymbolTransfer task number "n" and PC memory data (set the top addressusing @S) to a ZW/JW-20CM at port "n.&

Seite 142

13·2513Setting range for "S"· Rising edge of the input signal (OFF to ON) [※ 3]Operation conditionsFlag[※4]PC model name W70H/100H JW50/70/1

Seite 143

13·261313-6 Application instruction using instruction system(1) F-202F-202OPCHF-202OPCHPORTCH·STfile NnSymbolSpecify the target station for inter-PC d

Seite 144

13·2713(2) F-204F-204SENDSend Data• Even addresses must always be used for indirect addressing (@コ0001, @b0173, etc. areprohibited).• For details of i

Seite 145

13·2813(3) F-205F-205RCVReceive Data• Even addresses must always be used for indirect addressing (@∫0001, @b0173, etc. areprohibited).• For details of

Seite 146

5·65(2) Installation of JW-20RSInstall the JW-20RS in the second slot from the left end using the two module attachment screws.Before installation or

Seite 147

13·2913[Example 2] In case of reading data of 8 bytes to slave station 01(8)Module number installing own station JW-20CM : 2Channel number using own s

Seite 148 - File number of communication

6·16Make sure to use the recommended models shown below for cables and connectors.Chapter 6 Processing of CablesMakerMitsubishi CableIndustries,. Ltd.

Seite 149 - File number

6·266-1 Processing cable end① Applicable cableHigh frequency coaxial cable: ME-5C-2V② Required toolsStripper for high frequency coaxial cable: CST-TM

Seite 150

6·36Internal conductor(annealed copper single wire)10mmInsulator(semi-transparent)From the previous pagePut a coaxial cable while remaining approximat

Seite 151 - 9-8 Error and treatment

6·4610 mm±0.5 mmA: 10±0.5 mmB: 4±0.5 mmBAScrew holderBlade cassetteCut the internal conductor of the coaxial cable,which is already cut by the stripp

Seite 152

6·566-2 Connector crimping procedure① Required tools: Hand-held crimping tool② Connector: ME-GP-01③ Processing procedureConnector partsShellSleeveCon

Seite 153 - (2) Flag

6·66Slightly widen the external conductor of thecoaxial cable, which is crimped to a contact onthe internal conductor, in order to smoothly enterthe s

Seite 154

Safety PrecautionsRead this manual and attached documents carefully before installation, operation, maintenance and checkingin order to use the machin

Seite 155

7·177-1 Cable trunk and branch lines① On the illustration of the cable wiring below, a bold line means a trunk and the thin lines branchedfrom the tr

Seite 156

7·27[1] Fixing of the cableIn order not to put any force on the cable and theJW-20CM, fasten the cable to an line nearby inputof a control panel or a

Seite 157

7·37[5] Grounding of power supply moduleMake sure to connect the GND terminal of the power supply module to a class-3 grounding.• If the power supply

Seite 158 - Communication monitor

7·47Remarks7-4 Waterproof and insulation processing of connectorsIn order to prevent water intrusion into the “T” branch connectors and the straight

Seite 159

7·57The recommended connector types are used.The connectors are securely locked.The connectors are insulated by T jacket or L jacket.The recommended c

Seite 160 - Port 5 error Port 3 error

7·677-7 Wiring method for adding a communication station[1] Branching methodWhen branching a line for an additional station, be sure to branch from t

Seite 161

7·77Another branch line from a branch line may not giveappropriate communication by reflection wave.The use of the same station number twice may cause

Seite 162

7·877-8 Wiring to power supply module[1] JW-1PU· Open the terminal block cover, fasten with the screw with torque of less than 12kg·cm.·A maximum of t

Seite 163

7·97[2] JW-2PU· Open the terminal block cover, fasten with the screw with torque of less than 12kg·cm.· Halt output lines can not be connected serial.

Seite 164

8·18Chapter 8 Remote I/O8-1 Description of remote I/O· If remote I/O slave module JW-20RS is installed on I/O modules located separately, one PC (mast

Seite 165

3) Use Danger• Don’t touch the terminal while the power is being supplied or you may have an electric shock.• Assemble the emergency stop circuit and

Seite 166

8·28·Rack panel can use 2 sets max. per slave station. But, unavailable for use I/O bus expansion adapter(JW-1EA,JW-2EA).· Special I/O module of JW mo

Seite 167

8·388-2 Data transfer required time and communication timing(1) Required time for data transferTime required for a master station to communicate with

Seite 168

8·48(2) Communication timing· For communication with slave stations, either of "synchronous" and "asynchronous" can be selectedfor

Seite 169 - Chapter 10 Computer link

8·58① Operational synchronousWhen more than one JW-20CM is installed while using the remote I/O function, set only one moduleas “operational synchrono

Seite 170 - 10-2 Communication method

8·68I / O 処理データ交換I / O 処理データ交換I / O 処理データ交換親局PC ZW-20CMZW-20RS I/Oユニット子局1ZW-20RS I/Oユニット子局2子局1との通信子局2との通信子局1との通信子局2との通信入力信号I/O処理I/O処理I/O処理I

Seite 171 - 10-3 Switch setting

8·78(4) Voltage interruption time of slave moduleThe voltage interruption operation of slave module is carried out for service interruption signal (PF

Seite 172 - 10-4 Command

8·888-3 Outline of switch and parameter setting procedureIn brackets: See pageStartPower “OFF” master/slave stationSet switch of master moduleSet swit

Seite 173

8·98(1) Switch setting of master module (JW-20CM)In brackets: See pageOperation procedureStartPower “OFF” master/slave stationRemove the setting switc

Seite 174

8·108Turn master module and slave modulepower “OFF.”Remove the setting switch cover of mastermodule JW-20CM.·With your fingertips over the top and bot

Seite 175

8·118From the previous pageSet LT (termination resistance) switch• When a JW-20CM master module is at eitherend the communication line, make sure tose

Seite 176

Configuration of this manualThe network module JW-20CM has three functions: "remote I/O," "data link," and "computer link&q

Seite 177

8·128From the previous pageSet LG (shield ground) switch· For communication lines, use a coaxial cable.· As coaxial cable is an unbalanced circuit,gro

Seite 178

8·138From the previous pageAttach label· Attach the remote I/O master station label tothis module, make setting “remote I/O masterstation function” cl

Seite 179 - CPfonoitidnocnoitarepO ataD

8·148(2) Switch setting of slave module (JW-20RS)Operation procedure All slave module in common for setting methodIn brackets: See pageStartPowe

Seite 180

8·158Power “OFF” master/slave stationSet output hold switch· Set this switch whether to "latch" or "turn OFFall points" of output

Seite 181

8·168From the previous pageSet STA. NO. (station number) switch· Set "STA. NO" (station number) in octalnotation in sequential numbers from

Seite 182 - )FFO(000

8·178From the previous pageSet LG (shield ground) switch· For communication lines, use a coaxial cable.· As coaxial cable is an unbalanced circuit,gro

Seite 183

8·188From the previous pageWrite in label· Write “FIX” and “STA. NO.” on label of remoteI/O slave station, make setting contents clear.Switch setting

Seite 184

8·198(3) Parameter setting of slave module (JW-20RS)Set the following parameter address after setting switch. Setting item varies with using I/O modul

Seite 185

8·208Operation procedureIn brackets : See page Set of prohibit the auto I/O table registration at power “ON” (parameter address 001002(8) = 03 (H))[8·

Seite 186

8·218[I/O table registration in case of using JW-I/O]1. In case of not setting dummy I/ORegister I/O table based on the installed I/O module. (Set par

Seite 187

Network module JW-20CMRemote I/O slave module JW-20RS- User’s Manual -Chapter 1. OutlineChapter 2. Safety PrecautionsChapter 3. System Configuratio

Seite 188 - Chapter 11 Support Tools

8·228Indicates in [ ] of each item mean as follows:(Example) Stop remote I/O operation [HEX (hexadecimal), bytes]This means to set “stop remote I/O

Seite 189

8·238RemarksFrom the previous pageWriting to the EEPROM, start operation [HEX (hexadecimal), byte]· Write “81(H)” into parameter address 003777(8) and

Seite 190

8·248"Only when using ZW model I/O module"①Select "number of I/O byte checking" function [OCT (Octal), bytes](Applied to item ① on

Seite 191

8·258"Only when manual I/O registration using the JW model I/O module"③ Set number of dummy I/O points [HEX (hexadecimal), bytes](Applied to

Seite 192 - 11-2 Remote function

8·268"Only when manual I/O registration using JW model I/O modules"④ Set type of I/O module [HEX (hexadecimal), byte](Applied to item ④ on p

Seite 193 - Satellite net

8·278"Only when using JW model I/O modules"⑤ Registration of I/O table [HEX (hexadecimal), byte](Applied to item ⑤ on pages 8·20 to 22)· Set

Seite 194 - (JW-50PG)

8·288"Only when using JW model I/O module"⑦ Set maximum rack and slot numbers [HEX (hexadecimal), bytes](Applied to item ⑦ on pages 8·20 to

Seite 195

8·298"Only when using JW model I/O module"⑧ Setting remote I/O top address [OCT (octal), word](Applied to item ⑧ on pages 8·20 to 22)· In or

Seite 196

8·308(4) Parameter setting of master module (JW-20CM)Set the following parameter address after setting switch. Setting item varies with using PC (JW m

Seite 197

8·318Operation procedureTurn ON the power switch on the master station PCConnnect support toolsStop PC operationStop operation of the remote I/Os (par

Seite 198 - Chapter 12 Specifications

Table of contentsChapter 1 Outline ...

Seite 199

8·328Parameter setting range<Fixed allocation>·When fixed allocation is used, set parameter within the range shown below:1 to n : Number of slav

Seite 200

8·338Display the contents of parameteraddress 003777 by hexadecimal.Stop PC operationSelect initial modeSelect parameter setting mode.Screen display o

Seite 201 - 12-2 JW-20RS

8·348• Remote I/O operation (communication) stops.• The PC continues operation. (Mode 1)• Only normal slave stations will continueoperation (communica

Seite 202 - Chapter 13 Appendix

8·358From the previous pageSet number of connected slave stations [DCM (decimal), byte]· Set number of connected remote I/O slave stations into parame

Seite 203 - 13-2 Switch setting table

8·368Write (80(H)) tooutput to a flag in003767(8)After converting into byte display to003766(8), write in file number 0 inhexadecimal notation.From th

Seite 204 - 13-3 Parameter memory table

8·378Write 81(H)Writing to the EEPROM of the JW-20CM, start operation [HEX (hexadecimal), byte]From the previous page· Write “81(H)” into parameter ad

Seite 205 - (8) are all 00(H)

8·388"Only when using fixed allocation"③ Enter the number of slave station I/O points [HEX (hexadecimal), bytes](Applied to item ③ on pages

Seite 206 - (8) Set contents

8·398"Only when using fixed allocation"④ Set blanks between stations [DCM (decimal), bytes](Applied to item ④ on pages 8·31 and 8·35)· Enter

Seite 207

8·408"Only when using manual allocation"⑤ Enter the I/O top addresses of slave stations 02 to 77 [OCT (octal), words](Applied to item ⑤ on p

Seite 208 - (8) I/Os are JW models

8·418[Single address and continuous address]·If a slave station's I/O area is not linked tothe previous slave station's I/O area, thisslave

Seite 209

Chapter 11 Support Tools ... 11·111-

Seite 210

8·428sserddA)8(noitatsevalSrebmun)8(--1020001020200020302000304020004050200050602000607020007001200001112000112120002131200031412000415120005161200061

Seite 211

8·438"Only when the master station is a JW model"⑦ Enter the I/O type for each slave station [Bit pattern, bytes](Applied to item ⑦ on pages

Seite 212

8·448"Only when the master station PC is a JW model and a JW model special I/O module is used asa slave station"⑧ Enter the data register ad

Seite 213

8·458 Top register addressEnter top address of each special I/O module, which can be allocated up to 64 points per unit, atfile addresses 000000

Seite 214

8·4688-4 Error and treatmentOperation status of the JW-20CM can be check by indication lamps, flags, or system memory.(1) Indication lamp① JW-20CMIndi

Seite 215 - (8) are all 91(H)

8·478Remarks• Replace the JW-20CM• Check the communication cableCheck the communicationcableCheck the communication cableReplace the JW-20CMCheck the

Seite 216 - Bit address 76543210

8·488② JW-20RSIndication lampJW–20RSC O M M ○S D ○R D ○C D ○L T ○T E S T ○E R R O R ○F A U L T ○ ○ S 0 ○ S 1 ○ S 2 ○ S 3 ○ S 4 ○ S 5 ○ S 6 ○ S 7emaN n

Seite 217 - ③ Data link slave station

8·498Replace the JW-20RS• Check the communication cable• Replace the JW-20RSCheck the communicationcable• Reinput the power• Decrease load of slave st

Seite 218

8·508(I/O error code of JW model)• When error numbers 98 through 9C(H) occur, the module will store “rack No.” and “slot No.” in theparameter address

Seite 219

8·518       D7 D6 D5 D4 D3 D2 D1 D0    コ0740 07 06 05 04 03 02 01   コ0741 17 16 15 14 13 12 11 10   コ

Seite 220 - Slot: 1 Slot: 0

1·11Chapter 1 OutlineUsing network module JW-20CM, you can construct a communications system (satellite net) whichcan easily send and receive an ON/OF

Seite 221 - (File 0)

8·528Error code stored to system memory#170#16053(H)CauseMeasureReplace the JW-20CMReplace the JW-20CMCheck the communicationcable and slave moduleErr

Seite 222 - HAM4-WJ,AM4-WZ7,6,5,4,3,2,2,0

8·538Remarks• The error code stored in the system memory #170 is shifted to #170 to #177 one after the other as newerrors occur. Thus, the system memo

Seite 223 - Top address for

8·548(4) Recovery method at communication errors① Check flow chartFirst communication?Does the error occur continuously?RecoverySee “When the communic

Seite 224

8·558② Check cable/connectorAs errors on the junction from the main cable to the drop cable or the contact failure on theconnecting point of each stat

Seite 225 - Completed receiving flag

8·56803(8)Remove the connector on point A, and turn ON the termination resistance of the master station.07(8)06(8)05(8)Masterstation04(8)BD7OFFA CDisc

Seite 226

8·578sserddaretemaraP stnetnoC eulavgnitteS777300)8(hctiwstratS10③ During initial communication (start-up of the system)Check the error code of master

Seite 227 - Port No

8·588Parameter setting range<Fixed allocation>·When fixed allocation is used, set parameter within the range shown below:1 to n : Number of slav

Seite 228 - Send Data

8·598④ When the communication error occurs instantaneously.Cause may be:• Noise on the communication line.• Fault of a communication module.• Fault of

Seite 229 - Receive Data

8·608⑤ When the communication error occurs continuously.Identify the error station.Specify the error’s station using the communication flag etc., (see

Seite 230 - Target Station

9·19Chapter 9 Data Link9-1 Description for data link function· The data link function us used to send and receive ON/OFF signals (relay link: max. 204