I/O Modules 171
Configuration and Parameterization of the I/O Modules
WAGO-I/O-SYSTEM 750
Bus System
5.4.1.8 2 DO I/O Module with 2 Bit Diagnostics per Channel
Module
Identification
hex
Identification
dec
750-506, 750-5dd 2 DO/4DIA-DI/4 DIA,
Diagnostics in the input process image
0x30 48
750-506, 750-5dd 2 DO/4 DIA 0x20 32
*750-506, *750-5dd 2 DO/4 DIA 0x00 0
Process Image Input Image
in [Bit]
Output Image
in [Bit]
Internal bus 4 4
Diagnostics in the input process image
Yes 4 2
PROFIBUS DP
No 0 2
PFC (CPU) 4
1)
(0
2)
) 4
1)
(2
2)
)
Parameter Value Meaning
I/O module is physically The I/O module process data is
plug fitted
*)
- supplied to the I/O module
not plug fitted - ignored by the coupler
Diagnostics is mapped into the
Input-PAB
The diagnostics information of the I/O module
is
(only for *-Modules) released - mapped into the input process image
locked
*)
- not mapped into the input process image
Diagnostics channel x The diagnostics information of the correspond-
ing channel is
released - transmitted to PROFIBUS DP master
locked
*)
- not transmitted to PROFIBUS DP master
Substitute channel x
0
*)
1
If, in the case of a PROFIBUS DP fault, the
switching of substitute values is enabled by the
coupler parameterization, this data is transmitted
to the periphery in the case of a fault.
*)
Default settings
Parameter (up to Firmware 06)
Offset
Information
0
7 6 5 4 3 2 1 0
0 0 Plug 0 Diag
En1
Diag
En0
0 1
1
7 6 5 4 3 2 1 0
0 0 0 0 0 0 1 1
2
7 6 5 4 3 2 1 0
0 0 0 0 0 0 SV1 SV0
Parameter (from Firmware 07)
Offset
Information
0
7 6 5 4 3 2 1 0
0 0 Plug PA-
Diag
0 0 0 1
1
7 6 5 4 3 2 1 0
0 0 0 1 0 0 1 1
2
7 6 5 4 3 2 1 0
0 0 0 0 SV1 Diag
En1
SV0 Diag
En0