178 • I/O Modules
Configuration and Parameterization of the I/O Modules
WAGO-I/O-SYSTEM 750
Bus System
5.4.1.12 8 DO I/O Modules with 1 Bit Diagnostics per Channel
Module
Identification
hex
Identification
dec
750-537, 750-5dd 8 DO/8 DIA-DI/8 DIA,
Diagnostics in the input process image
0x30 48
750-537, 750-5dd 8 DO/8 DIA 0x20 32
Process Image Input Image
in [Bit]
Output Image
in [Bit]
Internal bus 8 8
Diagnostics in the input process image
Yes 8 8
PROFIBUS DP
No 0 8
PFC (CPU) 8
1)
(0
2)
) 8
Parameter Value Meaning
I/O module is physically The I/O module process data is
Plug fitted
*)
- supplied to the I/O module
not plug fitted - ignored by the coupler
Diagnostics channel x The diagnostics information of the correspond-
ing channel is
released - transmitted to PROFIBUS DP master
locked
*)
- not transmitted to PROFIBUS DP master
Substitute channel x
0
*)
1
If, in the case of a PROFIBUS DP fault, the
switching of substitute values is enabled by the
coupler parameterization, this data is transmitted
to the periphery in the case of a fault.
*)
Default settings
Parameter
Offset
Information
0
7 6 5 4 3 2 1 0
0 PFC Plug
PA-
Diag
0 0 1 1
1
7 6 5 4 3 2 1 0
0 0 0 1 1 0 1 1
2
7 6 5 4 3 2 1 0
SV3
Diag
En3
SV2
Diag
En2
SV1
Diag
En1
SV0
Diag
En0
3
7 6 5 4 3 2 1 0
SV7
Diag
En7
SV6
Diag
En6
SV5
Diag
En5
SV4
Diag
En4