72 • Programmable Field Bus Controller 750-833
Programming of the PFC with WAGO-I/O-PRO
WAGO-I/O-SYSTEM 750
Bus System
1. Start the WAGO-I/O-PRO software via 'Start/Programs' or by double
clicking on the WAGO-I/O-PRO symbol on your desk top.
2. In the "Online" menu click on the "Communication parameters" menu
point. The dialog "Communication parameters" opens.
3. In the selection window mark the desired driver on the right-hand dialog
side (i.e. "Serial (RS232)", to configure the serial connection between PC
and the controller).
4. In the center window of the dialog, the following entries have to appear:
-Parity: Even
-Stop bits: 1
If necessary, change the entries accordingly.
You can now commence testing the controller.
Note
To be able to access the controller, ensure that the operating mode switch of
the controller is set to the center or the top position.
5. Under "Online" click on the "Log-on" menu point to log into the controller.
(The WAGO-I/O-PRO Server is active during online operation. The
communication parameters cannot be polled.)
6. If there is not a program in the controller, a window appears asking whether
or not the program is to be loaded. Confirm with "Yes". Subsequently the
current program will be loaded.
7. As soon as the program is loaded, you can start the program via the
"Online" menu, menu point "Start". At the right-hand end of the status bar,
the system signals "ONLINE RUNNING".
8. To terminate the online operation, return via the "Online" menu and click
on the "Log-off" menu point.