Sharp IQ-8000 Installationshandbuch Seite 75

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 125
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 74
7.8 Communicating with Multiple IQ-400s (via RS-485)
Once the PC host is connected to one IQ-400, the next IQ-400 can be connected by wiring from
P3 from the first IQ-400 to P4 in the next IQ-400. This format can be repeated in up to 16
IQ-400s. In addition, any combination of MicroLPMs and IQ-400s can be configured up to the 16
total limit on a single RS485 channel. LiNC-NET supports up to 4 channels (total of 64 IQ-400/
MicroLPMs). See the next page for the IQ-400 to MicroLPM wiring connection.
NOTE: For UL 1076 installations, refer to the Linc-Net Admin Guide.
7.8.1 Wiring Diagram of Multiple IQ-400s and Other Panels
Page lxii of 110 IQ-400 Installation Manual 33-10057-001-C
Seitenansicht 74
1 2 ... 70 71 72 73 74 75 76 77 78 79 80 ... 124 125

Kommentare zu diesen Handbüchern

Keine Kommentare