Sharp JX-9400 Technical Information

Stöbern Sie online oder laden Sie Technical Information nach Drucken & Scannen Sharp JX-9400 herunter. Sharp JX-9400 Technical information Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 211
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen

Inhaltsverzeichnis

Seite 2

5.10 Global heat recovery efficiency versus nominal heat exchangereffectiveness measured in several units 965.11 Seasonal average coefficient of performanc

Seite 3

indoor air quality at a lower energy cost. Once again, measurements may help incommissioning and diagnosing failures.Energy in air handling unitsEnerg

Seite 4 - Claude-Alain Roulet

Figure 5.1, a psychrometric chart for air, shows several characteristics ofhumid air. The curves show the water content of air as a function of itstem

Seite 5

Figure 5.2 illustrates the paths of temperature and water content of air forheating and humidifying outdoor air in winter, at 08C and 80 per cent rela

Seite 6 - Contents

slowly if the air is in contact with massive structures that were cooled downbefore, for example, by strong airing during the cool night.Mechanical co

Seite 7

.From the indoor env ironment, heat loads and solar gains. This way ,common in tropical climates, saves the investment of the heating system,and heati

Seite 8 - List of Figures and Tables

To improve energy efficiency, mechanical ventilation systems are oftenequipped with heat recovery for recovering the heat contained in exhaust air.This

Seite 9

can be transferred from the warm side to the other. The heat recovery efficie ncyof these exchangers ranges from 60 to 80 per cent, depending on the typ

Seite 10 - List of Figures and Tables ix

Placing both fans on the same side results in a large pressure differentialthrough the rotating heat exc hanger, thus increasing leaks. A parasiticreci

Seite 11

The enthalpy flow, H, is the product of mass airflow rate and specificenthalpy, h:H ¼ Qh ð5:5Þwhere  is the density of air.At ambient temperature, a nu

Seite 12 - List of Figures and Tables xi

Leakage through heat exchangersSome heat exchangers let some air leak between both air channels. This is inmost cases not expected, since there are ve

Seite 13 - Preamble

7.4 Student distribution for 1, 2 and 5 degrees of freedom comparedto the normal distribution 1587.5 Confidence limit divided by standard deviation ver

Seite 14 - Introduction

rates. If these pressure differentials are significantly larger than the nominalvalues, the wheel should be cleaned.Indication on how to measure pressur

Seite 15 - Outdoor airflow rate

In simplified methods to calculate heating (or cooling) demand of buildings,ventilation heat loss, V, is often calculated by (CEN, 1999, 2007):V¼_mmð

Seite 16 - Recirculation rates

We have mentioned abo ve the following recirculation rates:External Re¼_mmi_mmo_mme¼_mme_mma_mmeð5:20ÞInlet to exhaust Rie¼_mmi_mmrs_mmi¼_mme_mmre

Seite 17 - Exfiltration

where:x¼_mmx_mmxþ_mmexfð5:32Þis the extraction efficiency, i.e. that part of the air leaving the ventilated volume,which is extr acted through the air

Seite 18 - Ventilation efficiency

which depend s on all parasitic airflow rates. When there is no external recircu-lation (Re¼ 0), Equation 5.37 simplifies to:G¼ð1  exfÞð1  RxsÞ1  R

Seite 19

Net energy saving and performance indexHeat recovery systems recover thermal energy but use electric energy for thefans. The net energy saving should

Seite 20 - Energy efficiency

Table 5.2 Measured airflow rates with experimental uncertainty band (whenavailable), total and specific fan power in audited unitsAirflow rates (m3/h) Fa

Seite 21 - Common techniques

in the three small units, and external recirculation above 20 per cent ismeasured in three large units. These leakages significantly affect heat recover

Seite 22 - Airflow Rates in Buildings

Best net ene rgy savings in large units (7 and 8 in Table 5.2) are 80,000–90,000 kWh per winter season, but unit 10 actually wastes as much energy.Sma

Seite 23

where: is the density of air,c is the heat capacity of air, is the temperature difference between exhaust air and supply air.The kinetic ene rgy giv

Seite 24 - Constant injection rate

6.6 VOC transfer rate in the experiments performed in both EPFLunits (%) 1236.7 VOC transfer rate in the EMPA experiments 1236.8 General IAQ strategie

Seite 25 - Pulse injection

consumption of electrical energy by the fan motor, and on the other hand thekinetic energy given to the air in duct.The fan efficiency is the ratio of u

Seite 26 - Airflow Rates in Buildings 5

The two ports of this manometer are connected to pressure taps located onboth sides of the fan (see Figure 5.13). Care should be taken to avoid too mu

Seite 27

simultaneously the r.m.s. voltage, U, between phase and neutral point, ther.m.s. current, I, running into each motor coil and the phase shift, ’, betw

Seite 28 - Airflow Rates in Buildings 7

on which the frequency, the voltage, the current and the fan motor power canbe displayed.Examples of applicationFan efficiencies were measured on severa

Seite 29 - Global system of equations

indoor environment quality and health or paying attention to possible damagesto buildings. If a decrease of thermal comfort was implicitly accepted, c

Seite 30 - Airflow Rates in Buildings 9

Table 5.4 Uses of energy in buildings, energy saving measures and their effects onindoor environment qualityEnergy use Energy saving measures Impact on

Seite 31 - Properties of the flow matrix

For each variant, the effect of the following changes in design and operation wassimulated:.with 50 per cent recirculation instead of no recirculation;

Seite 32 - Airflow Rates in Buildings 11

per day), ventilation strategies have a minor influence on heating energy demand.The air may be either heated by coils in the supply air or by radiator

Seite 33

a rotating heat exchanger (see Chapter 6, ‘Rotating heat exchangers’), has anegligible effect on energy demand.Infiltration or exfiltration through a lea

Seite 34 - Airflow Rates in Buildings 13

6Contaminants inAir Handling UnitsThe purpose of mechanic al ventilation systems is to supply appropriateamounts of clean air and to evacuate vitiated

Seite 35

PreambleThis book includes information already published by the author in scientificjournals and in an Air Infiltration and Ventilation Centre (AIVC) te

Seite 36 - Airflow Rates

DuctsThe duct material and the manufacturing process has the biggest effect on theperceived air quality (Bjo¨rkroth et al., 2000). Depending on the mac

Seite 37 - Source: Roulet et al., 2000a

The effect of airflow on the perceived air quality from ducts was relativelysmall and is probably insignificant in normal applications. Increasing theair

Seite 38 - Velocity traverse

Rotating heat exchangersRotating heat exchangers are not themselves sources of contaminants, but theymay transfer contaminants from exhaust to supply

Seite 39 - Tracer gas dilution

such that a sector of it that contains exhaust air passes first through the purgingchamber. The author has seen wheels turning the wrong way!In additio

Seite 40 - Source: Awbi, 2007

Figure 6.7 shows that certain categories of volatile organic compounds(VOCs) are easily transferred by a sorption transfer mech anism. Among thetested

Seite 41 - Tracer gas injection ports

Selecting the panelThe subjects are selected from a group of at least 50 applicants of ages rangingfrom 18 to approximately 35 years old. There is no

Seite 42 - Source: Roulet et al., 1999

The 2-propanone gas is evaporated in the PAP by placing one or more 30 mlglass bottles filled with 10 ml of 2-pr opanone and making different holes in t

Seite 43

.mechanical air supply with filtered air;.mixing ventilation with a certai n minimum ventilation rate.During the tests, the background level of 2-propa

Seite 44 - Node by node method

pollution of concentrations of 2-propanone unknown to them by makingcomparison with the milestones. On the third, fourth and fifth days, traininginclud

Seite 45

of Figure 6.10. The concentration of these VOCs in the air is analysed at thefour locations shown in Figure 6.10. Locations C6and C3should be farenoug

Seite 46

IntroductionWhy ventilate?Without ventilation, a building’s occupants will initially be troubled by odoursand other possible contaminants and heat. Hu

Seite 47

Air sampling and analysisAir at the four locations is sampled with a pump through small tubes filled withan adsorbing medium (for example, activated ch

Seite 48 - Eliminating some equations

Wal et al., 1998). These lists can inspire a selection of compounds to include inthe mix. However, the total number of compounds should not be too lar

Seite 49 - Simplest way

unit, however, was found with the wheel turning in the wrong way, making thepurging sector inactive.The measured ventilation efficiency in the EMPA acad

Seite 50

and rotates at 5 rpm. The diameter of one honeycomb cell is 1.5 mm. The wheelhas no purging sector and the fans are not in their ideal positions. This

Seite 51

Results of all experiments are shown in Tables 6.6 and 6.7.Evidence for adsorptionLeakage and entrained air would result in the same recirculation rat

Seite 52

experiments, the smallest recirculation rates are for limonene. They are close tothe rates that could be expected from leakage or entrained air.At the

Seite 53 - Less than four tracer gases

unity. The average difference between recirculation rates is 22 per cent, close tothe recirculation rate resulting from internal leakage in the EMPA un

Seite 54 - Planning tool

.Strategies that affect the design of the HVA C system – design principles andinnovative design strategies.For both of these categories, IAQ strategies

Seite 55 - Simple measurement using CO

Table 6.9 Checkpoints in HVAC units in visual inspectionComponent passed failOutdoor chamberAccess door: exists but closed hhChamber is clean (no dirt

Seite 56

Table 6.10 IAQ strategies for filtersDesign OperationPrevent filters from becoming a source of pollutionSelect a low-polluting new filterCondition (bake)

Seite 57

However, when the outdoor temperature excee ds indoor temperatures, it maybe wise to reduce the ventilation rate, only allowing high levels of ventila

Seite 58

Table 6.11 IAQ strategies for ductsDesign OperationPrevent ducts from becoming a source of pollutionUse duct processed withou t oil, and whichdoes not

Seite 59

Table 6.12 IAQ strategies for rotating heat exchangersDesign OperationSelect a wheel equipped with purgingsector and install it with the purgingsector

Seite 60 - Ventilation Efficiency

Notes1E´cole Polytechnique Fe´de´rale de Lausanne (Swiss Federal Institue of Technology ofLausanne).2 Swiss Federal Research Institute for Materials.T

Seite 61 - Air exchange efficiency

7Common Methodsand TechniquesExpressing concentrations and flow ratesCoherent unitsWhen using equations, such as Equation 2.7, to model ventilation sys

Seite 62 - Source: Roulet, 2004

withMM ¼PiMiniPinið7:3Þbeing the average molar mass of the mixture. For dry air,MM ¼ 28:96 g/mole.The relative change in density is then:¼MMMM

Seite 63 - Measurement method

In a mixture, every gas, x, occupies the whole volume, V:V ¼nxRTpxð7:8ÞThe relations between mass concentration, Cm, molar concentration, CM, andvolum

Seite 64

Item 5 is important mainly if the concentration is relatively high (for example,0.1 per cent or higher). For this reason and to achieve also items 3,

Seite 65 - Concentration [ppm]

potentially analyse any tracer. Table 7.3 shows their background concentra-tions in outdoor air.It can be seen in Tables 7.2 and 7.4 that no tracer co

Seite 66

Mixing tracer gasesPerfect mixing of tracer gas in the air of the measur ed zone or in the measuredduct is essential when determi ning the airflow rate

Seite 67

maintained under pressure. It is noted, however, that these two conditionscomplicate the experimental arrangement since control leads must extend toth

Seite 68

Measured airflow rates differ from the design values in many ventilationsystems. Figure 0.2 shows the relative differences between measured anddesign out

Seite 69 - Source: Roulet et al., 1998

Sampling methodsSamples of air containing tracer gases need to be taken for analysis. There areseveral sampling methods, each one being adapted to a p

Seite 70

tight caps. Properly used passive samplers adsorb all the tracers that are in theair enter ing the sampler. They are used to obtain a quantity of trac

Seite 71

As an example, for an airflow rate of 100 l/h, that is 28  106m3/s, theminimum pipe inner diameter will be 2.6 mm to have an air speed of 5 m/s.In th

Seite 72

Remember, however, that, in order to achieve good mixing, it is advanta-geous to inject the tracer continuously whenever possible. A series of shortpu

Seite 73 - The model matrix M

up to several minutes for gas chromatographs or multi-tracer infraredanalysers. Faster analysis will enable more frequent sampling of each zoneand hen

Seite 74 - Condition of the model matrix

vapour and CO2present at high concentrations in the air. Filters are used tominimize the effect but humidity should be measured simultaneously tosome t

Seite 75 - Factorial designs

this field. Only ions having a charge-to-mass ratio that corresponds to a givenradio frequency reach an orifice at the end of that path and pass into an

Seite 76 - 3-D designs

Gas chromatographyA puff of the sampled air is injected into a separating (chromatographic)column, a tube in which adsorbent material is packed. This c

Seite 77

By making the prescr ibed number of strokes of the hand-held bellows, thecorrect amount of air is drawn through the tube. This enables the tracer gase

Seite 78

Linear least square fit of the first kindSuch methods are used to find the coefficients of leakage models of Equations4.1 or 4.2 in fa n pressurization (se

Seite 79

measured recirc ulation rates are compared in Figure 0.3. These are seldom thesame. Even worse: as shown in Figure 0.4, out of 27 units planned withou

Seite 80 - Measurement methods

Confidence in the coefficientsThe variances on the linear coefficients of the regression of the first kind areusually estimated using the following relation

Seite 81

Regression of the second kindWhen there are uncer tainties in both axes, there is no reason to emphasize the xaxis, and the same procedure can be foll

Seite 82 - Reductive sealing

where "yand "xare the experimental errors on y and x respectively anddeduce a corr esponding value of a using Equation 7.16. This recipe doe

Seite 83

will be obtained, and a correlation between C and n will be found: the larger Cvalues correspond to the smaller n and vice versa. A good identification

Seite 84 - Density corrections

the a posteriori information. T his new distributio n:ðzÞ¼C exp 12fðzÞTC1TðzÞþðz  zpÞTC1zðz  zpÞghið7:41ÞFrom this distribution, the z vector

Seite 85 - Two measurement points

Generally, an instrument does not directly give the required information. Inmost cases, several measurements are combined to obtain the needed value.

Seite 86 - Airtightness 65

domain. The statistical method allows one to obtain more information on thereliability of the results.Because of rando m reading errors and uncontroll

Seite 87

Variance and standard deviationA figure representing the importance of the scattering around the average valueis the mean square deviation or variance:

Seite 88 - Airtightness of buildings

The confidence interval [c; c] of the normal distribution is obtained bysolving the equation:P ¼ erfðc=ffiffiffi2pÞð7:57Þfor a given value of P.If the norma

Seite 89 - External fan

more detail in statistical tables such as Zwillinger (2003)) and in mostmathematical software packages.Confidence interval of the Gaussian distribution

Seite 90 - Leakage visualization

the design and measured exfiltration ratios, i.e. parts of the supply air leakingthrough the building envelope in 30 units.Ventilation efficiencyAn efficie

Seite 91 - The stack effect method

Hence, we can state: ¼hxiIcð7:65ÞP is the probability that the confidence interval contains the ‘true’ value. P ischosen a priori, in practice betwee

Seite 92 - Airtightness 71

the infinitely small increments dxiby the absolute error xiand by summing theabsolute values:yj¼Xi@fj@xixið7:67ÞIf only arithmetical operati

Seite 93 - Neutral height method

represented by a vector x and a matrix A. The question is: which is theresulting error y on the vector y, which is the vector containing the final r

Seite 94 - Airtightness 73

the partial derivatives are computed as above and we get finally:s2yi; yj¼Xklmnikyljmyns2aklamnþXklikjls2xkxlþXklmnðikyljm jkylimÞs2aklxmð7:7

Seite 95 - Pressurization method

and the matrix norm is subordinated to the vectorial norm jxj if:jAj¼maxjAxjjxjfor any x 6¼ 0 ð7:85ÞThe subordinated norm is the smallest matrix nor

Seite 96 - Flow rate difference method

where 1and nare respectively the largest and the smallest eigenvalues ofAHA. This number is the spectral condition number.Constant absolute errorIf

Seite 97 - SealSeal

From which, using the method described in Chapter 1, ‘Zone by zonesystems of equations’, we get the airflow rates to and from each zone [m3/h]shown in

Seite 98 - Related to Energy Efficiency

ReferencesAeschlimann, J.-M., C. Bonjour and E. Stocker, eds, 1986, Me´thodologie et Techniquesde Plans d’Expe´riences: Cours de Perfectionnement de l

Seite 99

Brown, S. K., M. R. Sim, M. J. Abramson and C. N. Gray, 1994, Concentrationsof volatile organic compounds in indoor air: A review, Indoor Air, vol. 4,

Seite 100 - Energy in air handling units

Hakajiwa, S. and S. Togari, 1990, Simple test method of evaluating exterior tightnessof tall office buildings, in E. M. H. Sherman, ed., ASTM STP 1067,

Seite 101

When assess airflows in buildings?Ventilation performance should be checked early to detect potential problemsand to optimize the overall performance o

Seite 102

Presser, K. H. and R. Becker, 1988, Mit Lachgas dem Luftstrom auf der SpurLuftstrommessung in Raumlufttechnischen Anlagen mit Hilfe der Spurgasmethode

Seite 103

Sandberg, M. and C. Blomqvist, 1985, A quantitative estimate of the accuracy of tracergas methods for the determination of the ventilation flow rate in

Seite 104 - Heat exchangers

Annex AUnit Conversion TablesIntroductionSI units are used throughout this book. Non-SI units are, however, of generaluse in air infiltration and venti

Seite 105 - Types of heat exchangers

AreaName Symbol m2cm2sq in sq ft sq yd1 square metre m21 104 1550 10.7639 1.195991 square centimetre cm21041 0.3937008 0.0328084 0.010936131 square i

Seite 106 - Rotating heat exchangers

PressureName Symbol Pa mbar mm H2OinH2O psi1 Pascal Pa 1 0.01 0.102 0.004 145.037  1061 millibar mbar 100 1 10.2 0.422 14.5037  1031 mm water colu

Seite 107 - Heat exchange efficiency

Annex BGlossaryItems in italics are additional entries in the glossary.Age of the air (or age of a contaminant)Average time period since the fresh air

Seite 108

adventitious openings), caused by pressure effects of the wind and/or theeffect of differences in the indoor and outdoor air density.Air infiltration char

Seite 109

Building componentGeneral term for any individual part of the building envelope. Usually appliedto doors, windows and walls.Building envelopeThe total

Seite 110 - Ventilated

Constant concentration techniqueA method of measuring ventilation rate whereby an automated sy stem injectstracer gas at the rate required to maintain

Seite 111 - Global heat recovery efficiency

Distribution effectivenessRatio of the average tracer gas or contaminant concentration to the concentrationthat could be reached, at equilibrium, in th

Seite 112

Ventilation and Airflow in Buildings

Seite 113

effectiveness of the ventilation in appropriately distributing the air in the venti-lated space or in evacuating contaminants emitted at a given locati

Seite 114 - Source: Roulet et al., 2001

Fan pressurizationGeneral term applied to any technique involving the production of a steadystatic pressure differential across a building envelope or

Seite 115 - Examples of application

Indoor air pollutionPollution occurring indoors from any source, i.e., from outside as well as insidethe building.Infrared gas analyserInstrument used

Seite 116

MixingThe degree of uniformity of distribution of outdoor air or foreign material in abuilding.Mixing fanSmall electric fan used to aid the mixing of

Seite 117

Piston-type ventilationSee displacement flow.Pitot tubeAnemometer measuring the difference between the pressure in a tube facingthe flow, in which the flo

Seite 118 - Energy for ventilation

Reductive sealing methodA method of determining the leakage of specific building comp onents bypressurizing the building and recording the leakage chan

Seite 119

Site analysisApplied to any tracer gas measurement technique where tracer gas concentrationsand air exchange rates are determined directly at the meas

Seite 120 - Measurement of airflow rate

Turnover time of a contaminantRatio of the mass of contaminant con tained in an enclosure to the mass flow rateof the contaminant source in this enclos

Seite 122

Indexabsolute error, 154active ways, 78adsorption, 123age matrix, 10age of the air, 39, 42, 174airage of, 39, 42, 174changeefficiency, 40leakage rate, 6

Seite 123

conductance, 176confidence interval, 28, 149, 154,155conservation equation, 1, 7, 177constant concentration, 3, 12, 176constant injection rate, 3, 12,

Seite 124

1995, 2003). This can, however, be avo ided by appropriate design and main-tenance. Chapter 5, ‘Energy effect of IAQ measures’, lists the sources andca

Seite 125

air change rate, 67and heat recovery, 89area, 67, 178characteristics, 180coefficients, 60, 64heat exchangers, 88visualization, 69least square fit, 27, 14

Seite 126 - Recirculation

tracer gas (Continued)injection, 21mixing of, 137pulse injection, 4, 12, 182sampling, 22techniques, 12trained panel, 113transfer of contaminants, 10un

Seite 127 - Heat recovery

1Airflow Rates in BuildingsThis chapter intends to help the reade r to measure airflow rates and air changerates in buildings and room s, independently

Seite 128 - Ductwork

outdoor environment is then:dmdt¼ I þ CoQoi CiQioð1:1Þwhere:m is the mass of tracer gas in the zone (kg);I is the injection rate of the tracer gas (k

Seite 129 - Air Handling Units

This solution can be simplified, depending on the way the tracer isinjected.Tracer decay, no injectionA suitable quant ity of tracer gas is injected to

Seite 130 - Source: Bjo

Constant concentrationUsing an electronic mass flow controller monitored by the tracer gas analyser,the concentration of tracer gas can be maintained c

Seite 131 - Humidifiers

Applying again the integral mean value theorem, we get:m ¼ Qs;ið0Þðtf0CðtÞdt with 0 <0< tfð1:20ÞCombining Equations 1.18 and 1.20, we get:Qið

Seite 132

concentration C (Ciindoors and Cooutdoors) by:Qe¼SCi Coð1:22Þwhere S is the CO2source strength, i.e. about 20 l/h. The equivalent outdoorairflow rate

Seite 133 - Source: Roulet et al., 2000

do not change during the measurement campaign. This section describes waysof interpreting the records of tracer gas injection rates and concentration

Seite 134 - Measurement protocols

where:mikis the mass of tracer gas k in zone i;Iikis the injection rate of tracer gas k in (or just upwind of ) zone i;Cjkis the concentration of trac

Seite 136 - Source: Bluyssen, 1990

C contains the differences in mass concentrations Cik C0kof gas k in zone i.I is the matrix containing the mass flow rates Iikof the tracer, k , in zon

Seite 137 - Training procedure

Properties of the flow matrixThe total outdoor airflow rate to each zone, i, is easily obtained by summing thecolumns of the flow matrix:Qi0¼XNj ¼1Qijð1:

Seite 138 - Principle of the method

sums of the  matrix are the mean age of air in the corresponding rooms:hii¼XNj ¼1ijð1:38ÞThis relation enables the measurement of the room mean ag

Seite 139 - Injection technique

The air mass conservation (Equat ion 1.23) is rewritten as:q0i¼ TiXNj ¼0qijð1  ijÞTjXNj ¼1qjið1  ijÞþViTidTidtð1:43ÞThese last two systems includ

Seite 140 - Ø 6 mm copper tube

.The long-term integral method, generally used with passive sources andsamplers, also gives a biased estimate of the average airflow rate. Since themea

Seite 141 - Example of application

.Constant injection used with long-term direct solution is simpler to use andmay give, under certain conditions, unbiased estimates of an average airfl

Seite 142

2Airflow Ratesin Air Handling UnitsAir handling units are designed to supply new air to the ventilated zone and toextract vitiated air from this zone.

Seite 143

placed in the flow, for example a nozzle, Venturi or sharp-edged orifice (ISO,2003). Alternatively, the air speed can be measured directly at a number o

Seite 144 - Evidence for adsorption

 is the reduction ratio, which is the ratio of the smallest diameter to thediameter of the pipe.The flow may be restricted with an orifice plate, a noz

Seite 145

from 0.05 to 5 m/s, and are well suited for speeds of 1–5 m/s, which are typical inventilation ducts.Helix anemometers measure the rotation speed of a

Seite 146 - HVAC systems

BUILDINGS|ENERGY|SOLAR TECHNOLOGYVentilation and Airflow in BuildingsMethods for Diagnosis and EvaluationClaude-Alain RouletLondon.Sterling, VA

Seite 147

Assuming that no trac er is lost in between, the mass balance of the tracer gasis, at steady state:I ¼ðC  C0ÞQ ð2:3Þwhere:C is the tracer concentrati

Seite 148

The methods described in the section on ‘Measurement of airflow rate in aduct’ (above) may of course be used to measure the ai rflow rates through grill

Seite 149

In principle, the method described above in ‘Tracer gas dilution’ can beapplied to each branch of a duct network. However, this requires as manytracer

Seite 150

expected tracer gas concentration of tracer k:Ik¼ CkQ01ð2:5ÞSampling points for concentration measurementsTracer gas concentrations are measured at se

Seite 151

bringing additional tracer into the analyser, thus biasing the concentrationmeasurement. To avoid this, use different colours for injection and samplin

Seite 152

gas conservation equations can be rearranged so as to obtain one system ofequations per node, giving all airflow rates entering in this node. At steady

Seite 153 - Common Methods

recirculated air passes through a leak between extract and supply parts of theair handling unit or through a purpose-installed duct. Alternatively, ve

Seite 154

Node 2, return I11¼ðC11 C31ÞQ12þðC61 C31ÞQ62þðC71 C31ÞQ72ð2:10Þ0 ¼ðC12 C32ÞQ12þðC62 C32ÞQ62þðC72 C32ÞQ720 ¼ðC13 C33ÞQ12þðC63 C33ÞQ62þðC73 C3

Seite 155 - Properties of tracer gases

This system of 27 equations when combined with the system of Equation 2.9can be solved in various ways to provide the six main airflow rates andpotenti

Seite 156

Simplest wayA method providing all airflow rates with the simplest solutions – henceprobably the least sensitive to measurement errors – is given below

Seite 157 - Source: Dietz et al., 1983

First published by Earthscan in the UK and USA in 2008Copyright # Claude-Alain Roulet, 2008All rights reservedISBN-13: 978-1-84407-451-8Typesetting by

Seite 158 - Mixing tracer gases

withQ46¼ TðP; 1ÞffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiðC402 C42Þ2I252þ I252ðC2402þ C242ÞðC402 C42Þ4sð2:28

Seite 159 - Tracer density problem

The bias resulting from the alias with Q72is not taken into account in theconfidence interval. If tracer 4 is used, we get:Leakage to node 2Q72¼ðC32 C

Seite 160 - Passive sampling

orQ04ffi Q24ðC3k C4kÞðC4k C0kÞ¼ Q12ðC6k C1kÞðC6k C3kÞðC3k C4kÞðC4k C0kÞð2:41ÞQ04¼TðP; 1ÞðC4k C0kÞ2ffiffiffiffiffiffif04pð2:42Þwheref04¼ðC6k C3kÞ2ðC3k C1kÞ

Seite 161 - Networks, pumps and pipes

with k 6¼ 2(k ¼ 4 is not recommended here).Q76¼TðP; 1ÞC7k C6kffiffiffiffiffiffif76pð2:52Þwheref76¼ Q226C23kþ Q246C24kþðQ26þ Q46 Q76Þ2C26kþðC3k C6kÞ2Q226þð

Seite 162

Planning toolThere are many types of air handling units, and, from our experience, each newmeasurement poses new problems. It is hence impossible to p

Seite 163 - Objective of the analysis

Leaks in the heat exchanger, as well as in the return air channel, weredetected with this measurement. Measurement in three other identical unitsin th

Seite 164

concentrations are in volumetric ratios. It is not possible with only one tracerinjected into the ventilated space to differentiate between outdoor air

Seite 165 - Mass spectrometry

with ¼nð1  RÞ1  R þ ið2:63ÞThe theoretical exponential can be fitted to the experimental points, as shownin Figure 2.11 depicting an actual experi

Seite 166

The recirculation airflow rate can then be calculated using:Q62¼ Q24 Q12ð2:66ÞwithQ62¼ TðP; 1ÞffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiQ224þ Q212qffi TðP ; 1Þffiffiffiffiffiffi

Seite 167 - Chemical indicator tubes

withR ¼QQffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffið1 þ RÞpð2:73ÞOr method CR ¼ 1 Q12Q24withR ¼ffiffiffi2pQQð1  RÞð2:74Þassuming that the relative error Q=Q is the same for bo

Seite 168 - Identification methods

ContentsList of Figures and Tables viiPreamble xiiIntroduction xiii1 Airflow Rates in Buildings 1Single-zone measurements 1Application to buildings, mu

Seite 169

3Age of Air andVentilation EfficiencyThe airflow patterns should, in principle, be organized in order that new airis brought to the head of the occupants

Seite 170 - Confidence in the coefficients

However, the more time a small volume of air spends in a room, the more itwill be contaminated by pollutants.Since there is a large number of air part

Seite 171 - Orthogonal regression

constant. In rooms with complete mixing, the room mean age of air equalsthe nominal time constant, and the air exchange efficiency is 50 per cent.Short-

Seite 172 - Bayesian identification

corresponding to the nominal time constant. The air exchange efficiency inthis very theoretical case is 100 per cent. At 99 per cent air exchange effi-cie

Seite 173

assumes that the tracer gas behaves the same as the air: no adsorption andsame buoyancy, which is the case if the tracer concentration is small. It ca

Seite 174 - Error analysis

To interpret the recorded tracer gas concentrations and obtain the age ofair, the background (or supply) concentration should first be subtracted froma

Seite 175 - A few statistics

The local mean age of air at any location is the integral (or zero moment)of the probability distribution:r¼ 0¼ð10FrðtÞdt ð3:8ÞThe first moment of th

Seite 176

where:Fjis the probability distribution at time t ¼ j t,Step-up case Fj¼ 1 Cð t0þ jtÞCð1ÞDecay case Fj¼Cðt0þ j tÞCð t0Þð3:16ÞN is the last measure

Seite 177 - Statistical distributions

withFj¼ TðP; 1ÞffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiCeðjt þ t0ÞCeðjt þ t0Þ2þCeðjt þ

Seite 178

a displacement ventilation system, as shown in Figure 3.6. The conferenceroom is 8 m by 10 m wide and 3 m high. It is completely embedded in an old,ma

Seite 179

Measurement methods 59Determining the leakage coefficients 63Corrections for standard conditions 65Ways of expressing the airtightness 66Airtightness of

Seite 180 - Most simple error analysis

efficiency was doubled, and the mean age of air was maintained despite areduction of the ventilation rate – and of energy use – by a factor two.Mapping

Seite 181 - Linear equations systems

straightforward, takes time and has its cost, the theory of experimentaldesign (Box et al., 1978) may help in providing a maximum of informationthroug

Seite 182

for which seven coefficients must be determined. Table 3.2 summarizes theminimum number of measurements needed.Location of the measurement pointsAn impo

Seite 183 - Upper bound of the errors

The criteria described below are used to establish the most efficientdesign.Criteria for location of the measurement pointsThe model matrix MFirst, let

Seite 184

If 2is the experimental variance of the measured variable v, the variance2(ve) of the estimated variable is:2ðveÞ¼rTðMTMÞ1r2ð3:36ÞA variance func

Seite 185

As mentioned above, the experimental domain is about 20 per centsmaller than the measured space, samples of air being taken at least 0.1 timesthe char

Seite 186

can be added to obtain a minimum design for a quadratic model, which has acondition number of 6.3 (see Figure 3.9).The 2-D full factorial design with

Seite 187 - References

the points 8, 5 and 2 can be deleted (in that order) giving finally a designhaving 12 points and a condition number of 4.8. Finally, deleting two morep

Seite 188

Example of applicationThe age of air was mapped in the conference room after the improvement,first in the empty room, and then with ten occupants sitti

Seite 189

4AirtightnessWhy check airtightness?Controlled airflows, having adequate flow rate and passing at the appropriatelocations are essential for good indoor

Seite 190

List of Figures and TablesFigures0.1 Design and measured outdoor airflow rate per person in12 buildings xv0.2 Relative difference between measured and d

Seite 191

ventilation rate. Maintaining air quality requires an increase in supply air,leading to energy wastage.Checking the airtightness of a building envelop

Seite 192 - Unit Conversion Tables

column) and the airflow rate through the fan is measur ed using any of thefollowing methods:.The airflow rate through a fan depends on the pressure diffe

Seite 193

Inverting this relationship gives the airflow rate resulting from a pressuredifferential:q ¼b þffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffib2 4app2að4:3ÞBy fitting one of t

Seite 194 - Mass flow rate

flow rates at each pressure using the method described in section ‘Determiningthe leakage coefficients’, below.Components that can usually be sealed incl

Seite 195 - Glossary

experiments is performed, enough equations can be written to compute theairflows through the various measured parts for each pressure step.For that pur

Seite 196 - Glossary 175

its absolute temperature, and as long as the pressure differential remains smallwith respect to the atmospheric pressure:q ¼ qmTTmð4:5Þwhere T and Tmar

Seite 197

intervals. If the coefficients a and b are known, the airflow coefficient C and theexponent n are calculated using:C ¼ expðaÞ and n ¼ b ð4:11ÞThe Etheridge

Seite 198 - Glossary 177

Using the subscript o for these standard conditions and no subscript for themeasurement conditions, then:Co¼ Coð2n 1Þoð1 nÞð4:15Þwhere  is

Seite 199

Virtual air change rateBy dividing the airflow rate at conventional pressure by the internal volume ofthe tested enclosure gives a virtual leakage air

Seite 200 - Glossary 179

in order to create a pressure difference large enough to minimize influencesfrom wind and temperature differences on the results. This pressure differen-t

Seite 201

3.1 Ventilation modes with typical airflow patterns and airchange efficiencies 413.2 Typical probability density curves for the age of the air 413.3 Typi

Seite 202 - Glossary 181

The overall airtightness of the structure and the size of the available fangovern the maximum volume of enclosure that may be pressurized. Even iflarg

Seite 203

case, the airtightne ss is not good enough and cold air enters the inhabited spacethrough cracks between wooden panels.The stack effect methodThis simp

Seite 204 - Glossary 183

there is a priori only one neutral plane at the height z0. The neutral plane is thegenerally horizontal plane in the building or part of it where the

Seite 205

measuring the air speed at several locations and integrating over the wholeopening or using a tracer gas.gQgþ tCtpðztÞnþðznzrbdðrCrpðzrÞnÞ¼0 ð4:2

Seite 206 - Glossary 185

top of the opening to observe the flow direction. The neutral level is locatedbetween the ingo ing and outgoing flow directions. Sensitivity can be incr

Seite 207

that Ti> To, by:Q ¼ QAToTi1=21 znH3=2znH3=2ffi QAð1  aÞ3=2 a3=2ð4:29Þwith a ¼znHwhere znis the height of the neutral level.The opening area

Seite 208

example, using plastic sheeting and adhesive tape. Inflated balloons are alsowell suited to seal circular ducts.Tracer gas injection and air sampling t

Seite 209

upstream end of the duct and its concentration is measured at both ends to givethe flow rate at each.The leakage of the whole supply or exhaust network

Seite 210

5Measurements and MeasuresRelated to Energy Efficiencyin VentilationEnergy in buildingsEnergy uses and indoor environment qualityEnergy is used in build

Seite 211

Passive and active ways to get high quality buildings.Passive ways are architectural and constructive measures that naturally providea better indoor e