the design and measured exfiltration ratios, i.e. parts of the supply air leaking
through the building envelope in 30 units.
Ventilation efficiency
An efficient airing supplies the occupants with fresh air and blows polluted, old
air in unoccupied spaces. The ventilation efficiencies in several rooms, assessed
using the method described in Chapter 3, are illustrated in Figure 0.6.
Rather high ventilation efficiency, indicating piston-type ventilation, can be
seen in rooms 6 to 10, which are high auditoriums. The normal-height rooms 2
to 5 present a complete mixing, while room 1 shows poor ventilation efficiency,
partly explained by the fact that supply and exhaust are both located at the
ceiling in this room.
These few examples clearly illustrate the usefulness of measurements to
detect dysfunction.
-25%
0%
25%
50%
75%
100%
-10% 0% 10% 20%
Measured
Design exfiltration ratio
Figure 0.5 Design and measured exfiltration ratios compared in 30 units
Source: Roulet et al., 2001a.
0%
20%
40%
60%
80%
100%
1 2 3 4 5 6 7 8 9 10
Ventilation efficiency
Figure 0.6 Ventilation efficiency in some ventilated areas
Note: Dark bands are uncertainty bars. Note that in one unit the efficiency is below 50
per cent, indicating shortcuts and dead zones.
Source: Figure drawn from a table published in Roulet et al., 2001a.
Introduction xvii