with
R ¼
Q
Q
ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
ð1 þ RÞ
p
ð2:73Þ
Or method C
R ¼ 1
Q
12
Q
24
with
R ¼
ffiffi
2
p
Q
Q
ð1 RÞð2:74Þ
assuming that the relative error Q=Q is the same for both airflow rates, and
taking into account that Q
12
¼ð1 RÞQ
24
.
The accuracy of the three methods for determining R is compared in
Figure 2.12. Me thod B (Equation 2.73) should be preferred at low recirculation
ratios, while meth od C (Equation 2.74) is best at large recirculation ratios.
Method A could be applied where the other methods cannot be used. Note
that the relative error R=R becomes very large for small recirculation ratios.
It is interesting to see that some interpretation methods of the same
measurements provide more accurate results than others, and that the best
way depends on the unit measured. Therefore, care should be taken to select
the most appropriate method.
0%
5%
10%
15%
0% 20% 40% 60% 80% 100%
Confidence interval of R
Recirculation ratio
A
B
C
Figure 2.12 Confidence interval of the recirculation ratio as a function of the
recirculation ratio itself for three assessment metho ds
Note: For this figure, the relative confidence intervals of injection rate and concentra-
tions are 5 per cent.
38 Ventilation and Airflow in Buildings