Table 6.9 Checkpoints in HVAC units in visual inspection
Component passed fail
Outdoor chamber
Access door: exists but closed hh
Chamber is clean (no dirt, leaves, loose insulation materials etc.) hh
Appropriate water drainage hh
Filters
Access door: closed airtight hh
Pressure difference meter is installed and operational hh
Chamber is clean and dry (no water on the bottom of the chamber) hh
No broken filters or visible leaks hh
Filters bags do not touch on the bottom of the chamber when the unit is
not in operation
hh
Filters are clean (commissioning) or not too dirty/smelly (100% of the back
side is not dark)
hh
Filters are of class F7 or better (fine filters) hh
Coils
Access door: exists, but closed airtight hh
Fins are clean and not damaged hh
No visible microbial growth (cooling coils) hh
Drip pan and drainage (cooling coils) hh
Rotating heat exchanger
Access doors on both sides hh
No significant leakage between supply and exhaust channels hh
Purging sector is installed on the warm side of the wheel hh
Wheel rotates in correct direction (wheel material passes in front of the
purging sector after having left the exhaust part of the unit)
hh
F5 or better class filters are installed upwind of the wheel in both ducts hh
Pressure difference between supply and exhaust is positive hh
Wheel stops automatically when heat recovery is smaller than the power
needed to turn the wheel
hh
Humidifier
Access door exists, but closed airtight hh
Clean water, no visible microbial growth or oil film hh
Drop separator and drip pan are clean (if applicable) hh
Drainage with siphon; clean hh
Humidifier automatically shuts down if the air handling unit is off hh
The humidifier runs dry when the HVAC unit is shut down hh
Ducts
Access door not blocked hh
No condensed water or microbial growth in the ducts hh
No pieces of construction materials, mineral wool etc in the ducts hh
No metal powder in the ducts hh
Amount of dust under limit value hh
Contaminants in Air Handling Units 127