Sharp JX-9400 Technical Information Seite 62

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 211
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 61
constant. In rooms with complete mixing, the room mean age of air equals
the nominal time constant, and the air exchange efficiency is 50 per cent.
Short-circuiting of air will also leave dead zones in the room, giving rise to
an efficiency that is lower than 0.5 (see Figure 3.1).
Table 3.1 shows the air exchange efficiency and the corresponding room
mean age of the air, assuming that the nominal time constant or the mean age
at exhaust is one hour.
Some typical probability density curves of the age of the air at the exhaust
are illustrated in Figure 3.2, the air exchange efficiency being used as
parameter. If the air is displaced like a piston, all air particles reach a given
location in the room at the same time, and they reach the exhaust at a time
Figure 3.1 Ventilation modes with typical airflow patterns and air
change efficiencies
Source: Roulet, 2004.
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
00.511.522.53
f(τ)
τ
η
25%
50%
66%
80%
90%
99%
Figure 3.2 Typical probability density curves for the age of the air
Note: The parameter is the air exchange efficiency.
Table 3.1 Nominal time constant and room mean age of the air corresponding
to the probability curves shown in Figures 3.2 and 3.3
Air exchange efficiency
a
25% 50% 66% 80% 90% 99%
Room mean age of the air hi 1.44 0.99 0.76 0.62 0.55 0.50
Age of Air and Ventilation Efficiency 41
Seitenansicht 61
1 2 ... 57 58 59 60 61 62 63 64 65 66 67 ... 210 211

Kommentare zu diesen Handbüchern

Keine Kommentare