Table 6.10 IAQ strategies for filters
Design Operation
Prevent filters from becoming a source of pollution
Select a low-polluting new filter
Condition (bake) new filters before use
Use another filtering method such as
electrostatic filtering or apply a two or
more phase filtering system
Keep the filter dry (by proper layout of air
intake section, heating of supply air with
pre-heater or heating filters for a certain
period)
Minimize micro-organisms (UV radiation)
Avoid snow penetrating in the HVAC
system by proper layout of air intake
section
Keep filter bags from lying on the bottom
of the filter chamber when the HVAC unit
is not in operation (preventing filters
absorbing water due to eventual rain or
snow penetration)
Change filter on time: depending on the
situation, traffic and other loads once in
1–12 months, but in general every six
months for highly polluted areas (town)
and one year for low-polluting areas
(countryside)
Check pollution effect regularly in
sensory, chemical and biological ter ms
Prevent outdoor air from bypassing the filter
Make certain the filter frame and sealing
seat have no leaks
Prevent outdoor air impurities from
passing the filter itself: proper choice of
filter type
Make certain the filter frame and sealing
seat have no leaks
128 Ventilation and Airflow in Buildings