100 • Fieldbus ECO-Coupler 750-343
LED Signaling
WAGO-I/O-SYSTEM 750
PROFIBUS
3.1.10.5 Fault Message via the Blink Code of the I/O LED
Fault Argument Fault Description Remedy
Fault code 1: Hardware and Configuration Fault
1 Overflow of the internal buffer
memory for the inline code
Replace the Coupler
2 Unknown data type Replace the Coupler
3 EEPROM checksum fault Replace the Coupler
4 Fault during writing into the
flash memory
Replace the Coupler
5 Fault during reading from the
FLASH memory
Replace the Coupler
6 Changed I/O module
configuration found after
AUTORESET
Adapt the configuration to the
changed physical node arrangement.
Load the configuration and start the
coupler by switching the supply
voltage off and on again.
7 Reserved Replace the Coupler
8 Timeout when writing into the
serial EEPROM
Replace the Coupler
Fault code 2: Not Used
-- -
Fault code 3: Internal Bus Command Fault
0 I/O module(s) has (have)
identified internal bus command
as incorrect
Check out at what point the
communication bus is interrupted.
Therefore disconnect the Profibus
cable from the coupler!. Then plug
the end module into the middle of
the node. Switch the coupler off and
on again. If the I/O LED continues
to flash, shift the end module again.
If there is only one module on the
coupler and the I/O Err LED is
illuminated, either this module or the
coupler is defective. Replace the
defective component.