68 Fieldbus ECO-Coupler 750-343
Configuration of I/O Modules
WAGO-I/O-SYSTEM 750
PROFIBUS
3.1.8.1.2 4 DI I/O Modules
Module Identification
hex
Identification
dec
750-402, 750-403, 750-408, 750-409, 750-414, 750-415,
750-423, 750-422, 750-424
0x10 16
*750-402, *750-403, *750-408, *750-409, *750-414, *750-
415, *750-423, *750-422, *750-424
0x00 0
Process Image Input Image
in [bit]
Output Image
in [bit]
Internal bus 4 0
PROFIBUS DP 4 0
Parameter Value Meaning
I/O module is physically The I/O module process data is:
plug fitted
*)
- supplied by the I/O module
not plug fitted - Set to zero by the Coupler
*)
Default settings
Parameter
Offset
Information
0
76543210
00Plug 00001
1
76543210
00000001
2
76543210
00000000
Plug
5
0
1
Module is physically not present
Module is physically present (default)
Italic Cannot be changed