88 • Fieldbus ECO-Coupler 750-343
Configuration of I/O Modules
WAGO-I/O-SYSTEM 750
PROFIBUS
3.1.8.5 Serial Interfaces
All serial interface modules have 2 bytes of extended configuration
information used for the identification on internal bus and the creation of the
mapping table. Additional 2 bytes follow which are reserved for future
options.
Module Identification
hex
Identification
dec
750-650, 750-651, 750-653, 750-654 (3 Byte) 0xB3 179
750-650, 750-651, 750-653, 750-654 (5 Byte) 0xB5 181
Process Image
Input Image
in [byte]
Output Image
in [byte]
Internal bus 4 (6) 4 (6)
PROFIBUS DP 4 (6) 4 (6)
Parameter Value Meaning
I/O module is physically The I/O module process data is:
plug fitted*) - supplied by the I/O module or
supplied to the I/O module
not plug fitted - set to zero by the Coupler or
ignored by the Coupler
Diagnostics channel x The diagnostics information of the
corresponding channel is
released - transmitted to PROFIBUS DP master
locked
*)
- not transmitted to PROFIBUS DP master
*)
Default settings
Parameter
Offset
Information
0
76543210
00Plug 00Diag
En0
00
1
76543210
11ID5 ID4 ID3 ID2 ID1 ID0
2
15 14 13 12 11 10 9 8
reserved
3
76543210
reserved
Plug
5
0
1
Module is physically not present
Module is physically present (default)
DiagEn0
2
0
1
Diagnostics locked (default)
Diagnostics released
ID5 .. ID0 Order number less 630 (e.g. 750-650 would be coded as (650-630) = 20
Italic Cannot be changed