Fieldbus ECO-Coupler 750-343 71
Configuration of I/O Modules
WAGO-I/O-SYSTEM 750
PROFIBUS
3.1.8.1.5 2 DO I/O Modules
Module Identification
hex
Identification
dec
750-501, 750-502, 750-509, 750-512, 750-513,
750-514, 750-517
0x20 32
*750-501, *750-502, *750-509, *750-512, *750-513,
*750-514, *750-517
0x00 0
Process Image Input Image
in [bit]
Output Image
in [bit]
Internal bus 0 2
PROFIBUS DP 0 2
Parameter Value Meaning
I/O module is physically The I/O module process data is:
plug fitted
*)
- supplied to the I/O module
not plug fitted - ignored by the Coupler
Substitute channel x
0
*)
1
If, in the case of a PROFIBUS DP fault, the
switching of substitute values is enabled by the
Coupler configuration, this data is transmitted to
the periphery in the case of a fault.
*)
Default settings
Parameter
Offset
Information
0
76543210
00Plug 00000
1
76543210
00000010
2
76543210
000000SV1 SV0
Plug
5
0
1
Module is physically not present
Module is physically present (default)
SV0
0
Substitute value for channel 1
SV0
1
Substitute value for channel 2
Italic Cannot be changed