26 • The WAGO-I/O-SYSTEM 750
Power Supply
WAGO-I/O-SYSTEM 750
PROFIBUS
The maximum input current of the 24 V system supply is 260 mA. The exact
electrical consumption (I
(24 V)
) can be determined with the following formulas:
ECO Coupler
I
(5 V) total.
= Sum of all the internal current consumption of the connected
bus modules
+ internal current consumption of the ECO coupler
750-613
I
(5 V) total.
= Sum of all the internal current consumptions of the connected
bus modules
Input current m I
(24 V)
= 5 V / 24 V * I
(5 V) total.
/ η
η = 0.80 (at nominal load)
Note
If the electrical consumption of the power supply point for the 24 V-system
supply exceeds 260 mA for the ECO coupler respectively 500 mA for the
750-613, then the cause may be an improperly aligned node or a defect.
During the test, all outputs, in particular those of the relay modules, must be
active.