Fieldbus ECO-Coupler 750-343 • 79
Configuration of I/O Modules
WAGO-I/O-SYSTEM 750
PROFIBUS
3.1.8.2.2 4 AI I/O Module
Module Identification
hex
Identification
dec
750-453, 750-455, 750-460, 750-463, 750-468 0x53 83
Process Image Input Image
in [byte]
Output Image
in [byte]
Internal bus 12 12
PROFIBUS DP 8 0
Parameter Value Meaning
I/O module is physically The I/O module process data is:
plug fitted
*)
- supplied by the I/O module
not plug fitted - set to zero by the Coupler
Diagnostics channel x The diagnostics information of the
corresponding channel is
released
*)
- transmitted to PROFIBUS DP master
locked - not transmitted to PROFIBUS DP master
*)
Default settings
Parameter
Offset
Information
0
76543210
00Plug 0 Diag
En1
Diag
En0
Diag
En3
Diag
En2
1
76543210
01ID5 ID4 ID3 ID2 ID1 ID0
2
15 14 13 12 11 10 9 8
reserved
3
76543210
reserved
Plug
5
0
1
Module is physically not present
Module is physically present (default)
DiagEn2
0
0
1
Diagnostics channel 3 locked
Diagnostics channel 3 released
DiagEn3
1
0
1
Diagnostics channel 4 locked
Diagnostics channel 4 released
DiagEn0
2
0
1
Diagnostics channel 1 locked
Diagnostics channel 1 released
DiagEn1
3
0
1
Diagnostics channel 2 locked
Diagnostics channel 2 released
ID5 .. ID0 Order number less 450 (e.g. 750-461 would be coded as (468-450) = 18
Italic Cannot be changed