96 • Fieldbus ECO-Coupler 750-343
LED Signaling
WAGO-I/O-SYSTEM 750
PROFIBUS
3.1.10 LED Signaling
The Coupler possesses several LED's for on site signaling of the Coupler
operating status or the complete node
Fig. 3-10: Display elements 750-343 g012120x
The upper four LEDs (RUN, BF, DIA, BUS) display the state of the
PROFIBUS communication.
The lower LED (I/O) displays the internal state of the complete node.
3.1.10.1 Blink Code
Detailed fault messages are displayed with the aid of a blink code. A fault is
cyclically displayed with up to 3 blink sequences.
· The first blink sequence (approx. 10 Hz) starts the fault display.
· The second blink sequence (approx. 1 Hz) following a pause. The number
of blink pulses indicates the fault code.
· The third blink sequence (approx. 1 Hz) follows after a further pause. The
number of blink pulses indicates the fault argument.