106 • PROFIBUS
Wiring
WAGO-I/O-SYSTEM 750
PROFIBUS
Further information
The PNO provides further documentation for its members in INTERNET:
- Technical descriptions
- Guidelines
http://www.profibus.com/
5.2 Wiring
On the PROFIBUS with RS 485 transmission technology all devices are
connected in a line structure. The bus line comprises of a twisted and screened
pair of wires.
The fieldbus line is specified in EN 50 170 as a line type A and must provide
certain line parameters. The line type B also described in the EN 50 170 is an
old type and should no longer be used.
Parameter Value
Wave resistance 135 ... 165 Ω
Operating capacity < 30 pF/m
Loop resistance 110 Ω/km
Wire diameter
*)
> 0.64 mm
Wire cross section
*)
> 0.34 mm
2
*)
The wire cross sections used must conform with connection possibilities on the bus plug.
Line type A allows maximum line lengths for a bus segment dependent upon
the transmission speed.
Transmission speed Max. bus segment length
9.6 / 19.2 / 45.45 / 93.75 kBaud 1200 m
187.5 kBaud 1000 m
500 kBaud 400 m
1500 kBaud 200 m
3000 / 6000 / 12000 kBaud 100 m
The plugs available on the market offer the possibility that arriving and
departing data cables can be directly connected to the plug. In this manner
drop cables are avoided and the bus plug can be connected to or disconnected
from the bus at any time without interrupting the data traffic. A cut-in type bus
connection is integrated in these plugs. Due to the capacitative load of the
subscribers and the resulting generated line reflection the connection plugs
used should have integrated length inductivity. This is indispensable for
transmission rates of > 1.5 MBaud.