Fieldbus ECO-Coupler 750-343 97
LED Signaling
WAGO-I/O-SYSTEM 750
PROFIBUS
3.1.10.2 Fieldbus Status
The upper four LED's signal the operating conditions of the PROFIBUS
communication.
LED Color Meaning
RUN green The RUN-LED indicates the correct power supply of the Fieldbus
Coupler.
BF red The BF-LED indicates that the communication functions via the
PROFIBUS.
DIA red The DIA-LED indicates an external diagnostics.
BUS red The BUS-LED signals a configuration fault.
RUN BF DIA BUS Meaning Remedy
off off off off No operating voltage to
the Coupler (status LED
of the Coupler supply
does not light up) or a
hardware fault is
present.
Check the voltage supply for
the bus coupler and replace the
bus coupler if necessary.
on on * off PROFIBUS interface
started, baud rate was
not yet recognized.
Check to see whether the
PROFIBUS is connected.
Check to see whether the baud
rate configuration on the
master is supported by the
coupler.
Replace the bus coupler
because there is a hardware
defect.
on blinks * off Baud rate recognized,
node not yet configured.
Check the configuration and
the slave addresses.
Load the configuration and
start the coupler by switching
the supply voltage off and on
again.
on blinks on blinks
cyclic
ally
Slave was incorrectly
configured.
Fault message via blink
code
Evaluate the blink code.
on off * off The Coupler is
exchanging data.
OK
on * on * The Coupler signals an
existing diagnostics.
The data exchange is
functioning without any
problems so that you may
obtain diagnostic information,
for instance on a cable break in
an analog input terminal.
* Not relevant