80 • Fieldbus ECO-Coupler 750-343
Configuration of I/O Modules
WAGO-I/O-SYSTEM 750
PROFIBUS
3.1.8.2.3 2 AO I/O Modules
Module Identification
hex
Identification
dec
750-550, 750-552, 750-554, 750-556 0x61 97
Process Image Input Image
in [byte]
Output Image
in [byte]
Internal bus 6 6
PROFIBUS DP 0 4
Parameter Value Meaning
I/O module is physically The I/O module process data is:
plug fitted*) - supplied by the I/O module
not plug fitted - ignored by the Coupler
Diagnostics channel x The diagnostics information of the
corresponding channel is
released - transmitted to PROFIBUS DP master
locked
*)
- not transmitted to PROFIBUS DP master
Substitute value channel x
0x0000 or 0x8000
0 or -32767
... 0x7FFF
... 32767
If, in the case of a PROFIBUS DP fault, the
switching of substitute values is enabled by the
Coupler configuration, this data is transmitted to
the periphery in the case of a fault.
*)
Default settings
Parameter
Offset
Information
0
76543210
00Plug 00000
1
76543210
10ID5 ID4 ID3 ID2 ID1 ID0
2
15 14 13 12 11 9 8 7
SubVal_Ch1_HB
3
76543210
SubVal_Ch1_LB
4
15 14 13 12 11 10 9 8
SubVal_Ch2_HB
5
76543210
SubVal_Ch2_LB
Plug
5
0
1
Module is physically not present
Module is physically present (default)
SubVal_Ch1 0x0000
:
0xFFFF
Substitute value channel 1
SubVal_Ch2 0x0000
:
0xFFFF
2
ID5 .. ID0 Order number less 550 (e.g. 750-550 would be coded as (550-550) = 0
Italic Cannot be changed