PROFIBUS • 107
Wiring
WAGO-I/O-SYSTEM 750
PROFIBUS
6 6
3 3
1 1
9 9
8
7
2 2
4 4
7
8
5 5
VP
390 W
390 W
220 W
RxD/TxD-PRxD/TxD-P
RTSRTS
RxD/TxD-NRxD/TxD-N
DGND
9 pole D-SUB
Connector with
Terminating Resistor
9 pole D-SUB
Connector
Further
Fieldbus Nodes
Pin3-BLine
Pin 8 - A Line
Series inductance = 110 nH
Fig. 5-1: Bus connection g1xx302e
Note
When connecting the subscriber ensure that the data lines are not mixed up.
The bus termination at the start and end of the bus line must be installed. The
bus connection requires the supply voltage VP from the device. For this
reason ensure that the slave unit installed on the bus termination, is always
supplied with voltage.
Due to the integrated length inductivity in the connection plug ensure that the
plug is installed without connected field devices as the missing capacity of
the device could cause transmission faults.
In order to achieve a high disturbance resistance of the system against
electromagnetic radiated interference ensure that a screened PROFIBUS cable
is used. Where possible connect the screen at both ends with good conduction
and using large surface area screen clips. In addition ensure that the cables are
laid separated from all power line cables if possible. With a data rate of ≥1.5
Mbit/s ensure that spur lines are avoided.
Further information
The PNO provides further documentation for its members in INTERNET.
Cable specification information can be obtained from, for example, the
„Installation Guideline for PROFIBUS-FMS/DP", 2.112
http://www.profibus.com/
Note
WAGO offers this screen connection system for the optimum connection
between fieldbus screening and function earth.