66 Fieldbus ECO-Coupler 750-343
Configuring the Process Data Channel
WAGO-I/O-SYSTEM 750
PROFIBUS
3.1.7 Configuring the Process Data Channel
The process data channel serves for the communication between the Coupler
and the higher ranking systems (Master or project and diagnostics PC).
This channel is allocated to the Coupler and can not be used. When designing
the node, this position should therefore always show “750-343 No process
data channel”.
Module Identification
hex
Identification
dec.
750-333 No process data channel 0x00 0
750-333 2 byte process data channel 0xB1 177
Process Image Input Image
in [byte]
Output Image
in [byte]
Internal bus 0 0
PROFIBUS DP 2 2
Parameter Value Meaning
I/O module is physically The I/O module process data is:
plug fitted
*)
- supplied by the I/O module
not plug fitted - set to zero by the Coupler
*)
Default settings
Parameter
Offset
Information
0
76543210
10000000
1
76543210
00100001
2
76543210
000000Reg
Intf
0
RegIntf
1
0
1
Register Interface switched off (750-343 No process data channel)
Register Interface switched on (750-343 2 byte process data channel)
italic Cannot be changed
Attention
One of these configuration modules has to be selected for the first module
slot of the configuration table. Otherwise, the bus coupler signals a
configuration error on the BUS-LED and in the status signal of the
PROFIBUS diagnostics if it was released when configuring the bus coupler.